Field Settings for FTX, FVXS Series
SiUS091601EA
209
Part 7 Trial Operation and Field Settings
Caution
Caution
Reference
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Replace the remote controller if you cut a jumper unintentionally
.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
4.3 Jumper and Switch Settings
Jumper for FTX18/24UVJU, FVXS series
Switch for FVXS series
For the location of the jumper and the switch, refer to the following pages.
FTX18/24UVJU: page 26
FVXS: page 28
Jumper
on indoor
unit PCB
Function
When connected
(factory setting)
When cut
JB
Fan speed setting when
compressor stops for
thermostat OFF.
(effective only at cooling
operation)
Fan speed setting;
Remote controller setting
The fan stops.
JC
Power failure recovery
function
Auto-restart
The unit does not
resume operation after
recovering from a power
failure. Timer settings
are cleared.
Switch
on indoor unit
PCB
Function
OFF
(factory setting)
ON
SW2-4
Upward airflow limit
setting
Exposed or half
embedded installation
Set the switch to ON
position when you install
the indoor unit
embedded in the wall to
avoid condensation.
Содержание FDMQ12RVJU
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181 ...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185 ...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190 ...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191 ...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter ...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A ...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...