Control Specification
SiUS091601EA
85
Part 4 Functions and Control
5.8 Outdoor Fan Control
1.
Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the compressor
is OFF.
2.
Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
3.
Fan OFF delay when stopped
The outdoor fan is turned OFF 60 ~ 70 seconds after the compressor stops.
4.
Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled as
well as normal operation.
5.
Fan speed control during forced operation
The outdoor fan is controlled as well as normal operation during forced operation.
6.
Fan speed control during POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7.
Fan speed control during indoor/outdoor unit quiet operation
The rotation speed of the outdoor fan is reduced by the command of the indoor/outdoor unit
quiet operation.
8.
Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
5.9 Liquid Compression Protection Function
Outline
The compressor stops according to the outdoor temperature for protection.
Details
Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below 0°C (32°F).
However, the operating range can be extended to the lowest temperature of –20°C (–4°F) by
changing facility setting. Refer to page 217 for details of facility setting.
Содержание FDMQ12RVJU
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181 ...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185 ...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190 ...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191 ...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter ...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A ...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...