5.6 Freeze-up Protection Control
Outline
During cooling operation, the signal sent from the indoor unit determines the frequency upper limit
and prevents freezing of the indoor heat exchanger. The signals from the indoor unit are divided
into zones.
Details
The operating frequency limitation is judged with the indoor heat exchanger temperature.
R4003644
5.7 Heating Peak-cut Control
During heating operation, the indoor heat exchanger temperature determines the frequency upper
limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
: The valves might drop when the outdoor temperature is low to protect the compressor.
Reset zone
Up zone
Keep zone
Dropping zone
Stop zone
13°C (55.4°F)
7°C (44.6°F)
3°C (37.4°F)
0°C (32.0°F)
5°C (41.0°F)
(Reference)
Indoor heat exchanger
temperature (R2T)
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
09/12 class
15 class
18/24 class
(°C)
(°F)
(°C)
(°F)
(°C)
(°F)
A
59
138.2
60
140.0
60
140.0
B
55
131.0
54
129.2
56
134.6
C
52
125.6
51
123.8
53
129.2
D
50
122.0
49
120.2
51
125.6
E
45
113.0
44
111.2
46
116.6
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R23928)
D
C
B
A
E
Содержание FDMQ12RVJU
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181 ...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185 ...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190 ...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191 ...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter ...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A ...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...