Field Settings for FDMQ Series
SiUS091601EA
211
Part 7 Trial Operation and Field Settings
3. Highlight the mode, and select desired “Mode No.” by using
(Up/Down)
button.
4. In the case of setting per indoor unit during group control (When Mode No. such as
,
,
,
are selected), highlight the unit No. and select “Indoor unit No.” to be set by using
(Up/Down)
button. (In the case of group setting, this operation is not needed.)
In the case of individual setting per indoor unit, current settings are displayed. And, SECOND
CODE NO. “ - ” means no function.
5. Highlight SECOND CODE NO. of the FIRST CODE NO. to be changed, and select desired
“SECOND CODE NO.” by using
(Up/Down)
button. Multiple identical mode number
settings are available.
In the case of setting for all indoor units in the remote control group, available SECOND CODE
NO. is displayed as “
” which means it can be changed. When SECOND CODE NO. is
displayed as “ - ”, there is no function.
6. Press
Menu/OK
button. Setting confirmation screen is displayed.
7. Select
and press
Menu/OK
button. Setting details are determined and field settings screen
returns.
8. In the case of multiple setting changes, repeat 3 to 7.
9. After all setting changes are completed, press
Cancel
button twice.
10. Backlight goes out, and
[Checking the connection. Please stand by.]
is displayed for
initialization. After the initialization, the basic screen returns.
20 22
23 25
<Service settings screen>
3
4
5
0
–
–
–
–
3
5
0
SECOND CODE NO.
In the case of individual
setting per indoor unit
In the case of group total
setting
Field Settings
Unit No
Mode
20
Setting
0
4
8
12
01
1
01
–––
–––
–––
–––
–––
–––
–––
–––
–––
–––
–––
–––
5
9
13
2
6
10
14
02
3 01
7
11
15
–
1
–––
–––
–––
5
9
13
–
–––
–––
–––
2
6
10
14
–
–––
–––
–––
3
7
11
15
–
0
4
8
12
01
–––
–––
–––
Unit No
Mode
10
Field Settings
Setting
FIRST CODE (SW) NO.
Press
Menu/OK
button.
Yes
<Setting confirmation screen>
6
7
No
Setting confirmation
Field Settings
Save the settings?
Yes
Setting
Press
Menu/OK
button.
Содержание FDMQ12RVJU
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181 ...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185 ...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190 ...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191 ...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter ...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A ...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...