SiUS091601EA
Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis
174
Reference
7.13 Electrical Box Temperature Rise
Error Code
L3
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above
A
.
The error is cleared when the radiation fin temperature drops below
B
.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above
C
and stops when the radiation fin temperature drops below
B
.
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Troubleshooting
Check No.17
A
B
C
(°C)
(°F)
(°C)
(°F)
(°C)
(°F)
09 class
82
179.6
65
149
70
158
12 class
90
194
75
167
81
177.8
15 class
90
194
64
147.2
81
177.8
18/24 class
92
197.6
70
158
77
170.6
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above
C
and stops when the radiation
fin temperature drops below
B
.
(R22998)
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power. Then, turn on
the power to restart the system.
Check the radiation fin
temperature.
Radiation fin dirty?
Check No. 19
Check the outdoor fan.
Error again or
outdoor fan activated?
Replace the outdoor unit
PCB (main PCB).
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Above
A
?
Check the installation
condition.
Go to
Check No. 17
.
Содержание FDMQ12RVJU
Страница 14: ...SiUS091601EA 9 Part 1 General Information 1 Applicable Models 10 2 Functions 11 Part 1 General Information ...
Страница 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Страница 132: ...Troubleshooting for FTX FVXS Series SiUS091601EA 127 Part 6 Service Diagnosis Reference Check No 01 Refer to P 181 ...
Страница 161: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 156 Reference Check No 14 Refer to P 185 ...
Страница 165: ...SiUS091601EA Troubleshooting for Outdoor Unit Part 6 Service Diagnosis 160 Reference Check No 18 Refer to P 190 ...
Страница 180: ...Troubleshooting for Outdoor Unit SiUS091601EA 175 Part 6 Service Diagnosis Reference Check No 19 Refer to P 191 ...
Страница 197: ...SiUS091601EA Check Part 6 Service Diagnosis 192 12 class 15 class Multimeter R23024 R25105 1 2 3 4 Multimeter ...
Страница 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Страница 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Страница 228: ...Piping Diagrams SiUS091601EA 223 Part 8 Appendix 1 2 Outdoor Unit RXL09QMVJU RXL12QMVJU 9 3D100008 3D100009A ...
Страница 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Страница 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...