Control Specification
SiUS071735EA
35
Functions and Control
2.5
Input Current Control
Outline
The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of frequency and takes priority
over the lower limit control of four way valve operation compensation.
Details
Frequency control in each zone
Stop zone
After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping zone
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level (depending
on the model).
09/12 class
15 class
18 class
24 class
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
A
(A)
12
12
12
12.5
18
B
(A)
7
7.5
8
10
10.75
12
11.5
C
(A)
6
6.5
7
9
9.75
11
10.5
Compressor Stop
Input current
Dropping zone
Stop zone
Keep zone
Reset zone
(R23249)
A
(A)
B
C
Содержание FDMQ09RVJU
Страница 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 138: ...Piping Diagrams SiUS071735EA 127 Appendix 1 Piping Diagrams 1 1 Indoor Unit FDMQ09 12 15 18 24RVJU C 4D112974A ...
Страница 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A ...