SiUS071735EB
Outdoor Unit
Printed Circuit Board Connector Wiring Diagram
14
4. Outdoor Unit
4.1 RX09/12R
Main PCB (PCB1)
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
1) S20
Connector for electronic expansion valve coil
2) S30
Connector for compressor
3) S40
Connector for overload protector (for RX09/12RMVJU(9)) / Connector for
overload protector and high pressure switch (for RX09/12RMVJU9A)
4) S71
Connector for DC fan motor
5) S80
Connector for four way valve coil
6) S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
7) HL1, HN1, S
Connector for terminal block
8) E1, E2
Terminal for ground wire
9) HR1, HR2
Connector for reactor
10)FU1, FU2
Fuse (3.15 A, 250 V)
11)FU3
Fuse (20 A, 250 V)
12)J6
Jumper for facility setting
Refer to page 129 for details.
12)LED A
LED for service monitor (green)
13)V2, V3, V150
Varistor
E1, E2
FU3
V150
V2
V3
FU1
FU2
HR1
HR2
S20
LED A
S90
S30
J6
S40
2P504947-57, 2P504947-90, 2P504947-91
HL1, HN1, S
S80
S71
Содержание FDMQ09RVJU
Страница 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 143: ...SiUS071735EB Piping Diagrams Appendix 132 1 Piping Diagrams 1 1 Indoor Unit FDMQ09 12 15 18 24RVJU C 4D112974A ...