
Troubleshooting
SiUS071735EB
89
Service Diagnosis
4.20 Four Way Valve Abnormality
Error Code
EA
Method of Error
Detection
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Error Decision
Conditions
The following condition continues over 10 minutes after operating for 5 minutes.
Cooling/Dry
A
–
B
< –5°C (
A
–
B
< –9°F)
Heating
B
–
A
< –5°C (
B
–
A
< –9°F)
A
: Room thermistor temperature
B
: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Содержание FDMQ09RVJU
Страница 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 143: ...SiUS071735EB Piping Diagrams Appendix 132 1 Piping Diagrams 1 1 Indoor Unit FDMQ09 12 15 18 24RVJU C 4D112974A ...