Check
SiBE12-713
280
Service Diagnosis
6.1.6
Installation Condition Check
Check No.07
Installation condition check
Normal
Change the position of the air
discharge grille or the
installation location.
Change the position of the air
discharge grille or the
installation location.
Clean the heat exchanger.
Change the installation
location or direction.
Check the outside air
temperature (temperature of air
taken in by the outdoor unit).
(The outside air temperature
shall be 46˚C or lower.)
Check
the allowable
dimensions of the air suction
and discharge
area.
Is
the air flow
blocked by obstacles or
winds blowing in the
opposite direction?
(R3048)
Abnormal
YES
YES
YES
Does
the discharged
air from other outdoor
unit cause an increase of
the suction air
temperature?
NO
NO
NO
Is the heat exchanger
very dirty?
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...