Troubleshooting
SiBE12-713
250
Service Diagnosis
5.12
OL Activation (Compressor Overload)
Remote
Controller
Display
E5
Outdoor Unit LED
Display
A
5
1
4
2
1
3
4
4
1
Method of
Malfunction
Detection
A compressor overload is detected through compressor OL.
Malfunction
Decision
Conditions
If the compressor OL is activated twice, the system will be shut down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
∗
The operating temperature condition is not specified.
Supposed
Causes
Refrigerant shortage
Four way valve malfunctioning
Outdoor unit PCB defective
Water mixed in the local piping
Electronic expansion valve defective
Stop valve defective
Troubleshooting
Check No.04
Refer to P.277
Check No.05
Refer to P.278
Check No.06
Refer to P.279
Check No.11
Refer to P.282
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the valve itself or
the coil.
Replace the four way valve
coil or the valve itself.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
(R4697)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Discharge pipe thermistor
disconnected?
YES
Malfunctioning
∗
Discharge pipe thermistor
NO
Functioning
Functioning
Check No. 11
Check the refrigerant line.
Malfunctioning
∗
Refrigerant shortage
∗
Water mixed
∗
Stop valve defective
Check No. 06
Check the thermistors
Malfunctioning
Functioning
Check No. 04
Check the electronic expantion
valve.
Malfunctioning
Functioning
Check No. 05
Check the four way valve.
Replace the outdoor unit
PCB.
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...