SiBE12-713
Troubleshooting
Service Diagnosis
247
5.10
Freeze-up Protection Control
Remote
Controller
Display
A5
Outdoor Unit LED
Display
A
5
1
4
2
1
3
4
4
4
Method of
Malfunction
Detection
Indoor unit icing, during cooling operation, is detected by checking the temperatures sensed by
the indoor unit heat exchanger thermistor and room temperature thermistor that are located in a
shut-down room.
Malfunction
Decision
Conditions
In the cooling mode, the following conditions (A) and (B) are kept together for 5 minutes.
(A) Indoor unit heat exchanger temperature
≤
–1°C
(B) Indoor unit heat exchanger temperature
≤
Room temperature –10°C
If the freeze-up protection control is activated 4 times continuously, the system will be shut
down.
(The 4-time counter will reset itself if any of the following errors does not occur for 60
minutes: OL, radiation fin temperature rise, gas shortage, and compressor startup.)
Supposed
Causes
Wrong wiring or piping
EV malfunctioning in each room
Short-circuit
Indoor unit heat exchanger thermistor defective
Room temperature thermistor defective
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...