Daikin EWYQ080DAYN Скачать руководство пользователя страница 19

EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35558-1B

Operation manual

18

Defining controller settings

The second 

ADVANCED

 screen of the usersettings menu also allows

the user to define settings for the controller.

MAIN MENU

:  set to 

GRAPHIC

  to let the main menu show the

graphical symbols or to 

TEXT

  to let the main menu show the

names of the menus.

LOGOUT TIMER

: set the time for automatic log out, between 01

and 30 minutes.

BUZZER IF SAFETY

:  to activate or deactivate the buzzer

sound when an error should occur.

BACKLIGHT TIME

:  to define the time (between 01 and 30

minutes) the light of the controller display will stay on after the
last manipulation of the controller buttons.

GRAPHIC READOUT

: to define if the graphical representation of

the first screen of the read out menu is present or not.

Submenu: Defrost

In the first screen, manual defrost operation can be activated for the
unit and circuits 1 and 2.

The second screen allows the user to select a minimum time
between each automatic 

DEFROST

 operation:

NORMAL

: normal time between defrost operations.

SHORT

: short time between defrost operations.

Submenu: Service menu

Only a qualified installer is allowed to enter the service menu.

Tasks of the timers menu

Checking the actual value of the software timers

As a protective measure and to ensure correct operation, the
controller's software features several countdown timers:

LOADUP (

LOADUP

 – refer to the thermostat parameters): starts

counting when a thermostat step change has occurred. During
the countdown, the unit is not able to enter a higher thermostat
step.

LOADDOWN (

DWN

 – refer to the thermostat parameters): starts

counting when a thermostat step change has occurred. During
the countdown, the unit will not be able to go to a lower thermo-
stat step.

FLOWSTART (

FLOWSTART

  – 15 sec): counts down when the

water flow through the evaporator is continuous and the unit is in
standby. During the countdown, the unit cannot start up.

FLOWSTOP (

FLOWSTOP

  – 5 sec): starts counting when the

water flow through the evaporator stops after the flowstart timer
has reached zero. If the water flow has not restarted during the
countdown, the unit will shut down.

PUMPLEAD (

PUMPLEAD

  – refer to the pump control settings):

starts counting whenever the unit is switched on. During the
countdown, the unit cannot start up.

PUMPLAG (

PUMPLAG

  – refer to the pump control settings):

starts counting whenever the unit is switched off. During the
countdown, the pump keeps running.

GUARDTIMER (

GRD11

/1

2

/

21

/

22

  – 180 sec): starts counting

when the compressor (circuit 1/2) has been shut down. During
the countdown, the compressor cannot be restarted.

ANTIRECYCLING (

AREC11

/1

2

/

21

/

22 

– 300 sec): starts

counting when the compressor (circuit 1/2) has started. During
the countdown, the compressor cannot be restarted.

MINIMUM RUNNING TIME (

M.RT

  - 120 sec) starts counting

when the compressor has started. During the count down, the
compressor will not be switched off by the thermostat function.

To check the actual value of the software timers, proceed as follows:

1

Enter the 

TIMERS MENU

. (Refer to the chapter 

"How to enter a

menu" on page 8

.)

The controller displays the actual value of the 

GENERAL

TIMERS

:  the loadup timer, the loaddown timer, the flowstart

timer, the flowstop timer (when the unit is on and the flowstart
timer has reached zero), the pumplead timer and the pumplag
timer.

2

Press the 

Ì

 key to check the compressor timers.

The controller shows the actual value of the 

COMPRESSOR

TIMERS

: the guard timers (one per circuit) and the antirecycling

timers (one per circuit).

Tasks of the safety menu

Listing activated safeties and checking the unit status

If the alarm buzzer is activated and the user presses the 

π

 key, the

controller automatically enters the safeties menu.

All active safeties are displayed: 

UNIT

/

CIRCUIT 1

/

2

WARNING

 or

NETWORK SAFETY

.

The controller will show the 

UNIT SAFETY

  screen of the

safeties menu when a unit safety was the cause of shutdown.

The controller will show the 

CIRCUIT 1

/

2 SAFETY

 screen of

the safeties menu when a safety of the circuit 1/2 was activated.

The controller will show the 

NETWORK SAFETY

  screen of the

safeties menu when a safety of the network was activated.

The controller will show the 

UNIT WARNING 

screen of the

safeties menu when a unit warning was activated.

1

Press the 

π

 key when the alarm buzzer is activated.

The appropriate safety screen with the basic information
appears. Press the 

 key to go directly to the history menu and

see the detailed information. These screens provide information
about the unit status at the moment of shutdown (see 

"Safety

menu 

π

" on page 13

).

2

If more than one kind of safety is active (indicated by means of

^

v

 or 

÷

), use the 

 and 

Ì

 keys to consult them.

Tasks of the history menu

Checking the safety info and the unit status after a reset

The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the circuit.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest shutdown.

To check the safety info and the unit status, proceed as follows:

1

Enter the 

HISTORY MENU

. (Refer to the chapter 

"How to enter

a menu" on page 8

.)

The controller enters the last 

HISTORY

  screen which contains

basic information of the moment of this shutdown.

2

Press the 

 and 

Ì

 keys to consult the other present 

HISTORY

screens.

3

Press the 

 key to see the detailed information.

NOTE

If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.

Содержание EWYQ080DAYN

Страница 1: ...OPERATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start...

Страница 3: ...p 15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Maximum running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency...

Страница 4: ...r supply intake 32 Liquid receiver 2 Condenser in cooling mode or evaporator in heating mode 17 Switchbox 33 Pump optional 18 Digital display controller behind service panel 34 Buffer tank optional 3...

Страница 5: ...nters the evaporator via an expansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p M12C M11C M15F M13F M14F R14T B1PL...

Страница 6: ...al The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phase protector general safety device The reverse phase protectors prevent the unit from...

Страница 7: ...ercurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWYQ080 100 and EWYQ180 250 K15S Fan overcurrent relay for circuit 1 only for EWYQ080 100 and EWYQ180 250 K16F Fancontactor for c...

Страница 8: ...ally installed protection devices are of the size and type specified in the installation manual Make sure that neither a fuse nor a protection device has been bypassed 3 Earth wiring Make sure that th...

Страница 9: ...k oriented modular structure Apart from the first section which gives a brief description of the controller itself each section or subsection deals with a specific task you can perform with the unit D...

Страница 10: ...n a unit with status NORMAL or STANDBY all other units with status NORMAL or STANDBY will be ON or OFF If the key is pressed on a unit with status DISCONNECT ON OFF only this unit will be ON or OFF Co...

Страница 11: ...ter temperature has not risen enough compared to previous switch off of the compressor FREE COOLING free cooling mode is active TIMER BUSY the actual value of one of the compressor timers is not zero...

Страница 12: ...work safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network the red light inside the key of the...

Страница 13: ...l informa tion about the current Ampere and voltage of the unit _v 0U4 013 6 11 12 H 012 0 21 22 H _ COOL INLSP1 012 0 INLET WATER 013 6 OUTLET WATER 007 0 AMBIENT 006 5 _ C1 TEMP READOUT C11 DISCHARG...

Страница 14: ...IC READOUT YES _v MANUAL DEFROST UNIT DEFROST OFF CIR1 DEFROST OFF CIR2 DEFROST OFF _ DEFROST MIN TIME BETWEEN DEFROST NORMAL ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the gene...

Страница 15: ...2 C12RH 00000hCS 00000 C12C 00000h H 00000h _ UNIT HISTORY 002 C21RH 00000hCS 00000 C21C 00000h H 00000h _ UNIT HISTORY 002 C22RH 00000hCS 00000 C22C 00000h H 00000h _ UNIT HISTORY 002 AI1 NONE AI2 NO...

Страница 16: ...control mode The unit is equipped with a thermostat which controls the cooling or heating capacity of the unit Select the appropriate mode MANUAL CONTROL manual control mode the operator controls the...

Страница 17: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 18: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 19: ...counting when the compressor circuit 1 2 has started During the countdown the compressor cannot be restarted MINIMUM RUNNING TIME M RT 120 sec starts counting when the compressor has started During th...

Страница 20: ...h REMOTE COOL HEAT indicates the position of the remote cool heat switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOISE indicates the status...

Страница 21: ...next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain t...

Страница 22: ...y devices are activated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety device...

Страница 23: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 24: ...essary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRECTIVE ACTION The sensor is broken or not correctly wired Check if the wiring is acco...

Страница 25: ...er quality refer to the installation manual of the unit for specifications of the water quality Water filters Make sure to clean the water filter in front of the evaporator water inlet once every 4 mo...

Страница 26: ...s load up requests of maximum 2 compressors at a time A Load up request of 1 compressor B No action C Load down request of 1 compressor D Inlet setpoint E Outlet setpoint INLET CONTROL Default value L...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...FO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PASSWORD 0000 TO LOGIN ENTER PASSWORD PASSWORD 0000 TO LOGIN _ COOLING HEATING MODE COOLING STARTUP BUSY READOUT MENU SETPOINTS...

Страница 29: ...ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1 OFF _ UNIT HISTORY 002 HP2 019 0b 050 8 LP2 004 4...

Страница 30: ...4PW35558 1B Copyright Daikin...

Отзывы: