Daikin EWYQ080DAYN Скачать руководство пользователя страница 11

EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35558-1B

Operation manual

10

2

Press the 

Ì

 key to enter the next screen of the readout menu.

MANUAL MODE

  or 

COOL INLSP1

/

2

  or 

COOL OUTLSP1

/

2

or 

HEAT INSLP1

/

2

  or 

HEAT OUTSP1

/

2

:  manual/automatic

control mode operation. If the automatic control mode is selected,
the controller will indicate the active temperature setpoint.
Depending on the status of the remote contact, setpoint one or
setpoint two is active.

INL WATER

: actual inlet water temperature.

OUTL WATER

: actual outlet water temperature.

AMBIENT

: actual ambient temperature.

3

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

TEMPERATURE

  screen of the readout menu provides

information concerning the discharge temperature of the
compressors (

C11

 and 

C12

/

C21

 and 

C22

).

4

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

C1

/

C2 TEMP. READOUT

  screen of the readout menu

provides information concerning the refrigerant temperature
(

REFR

) and coil temperature of circuit 1/circuit 2.

5

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

ACT. PRESSURES

  screen of the readout menu provides

information concerning the actual pressures of circuit.

HP1/2

: high pressure of the refrigerant in circuit 1/2. The first

number stands for the pressure in bar, the second number
stands for the bubble point saturation temperature in degrees
Celsius.

LP1/2

: low pressure of the refrigerant in circuit 1/2. The first

number stands for the pressure in bar, the second number
stands for the dew point saturation temperature in degrees
Celsius.

LOWNOISE

: at the bottom of the first screen, the status of the

lownoise setting is shown (

Y

=active or 

N

=not active).

6

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

UNIT STATUS

  screen of the readout menu provides

information concerning the status of the different circuits.

C11

and 

C12

: actual status of circuit 1 (

ON

 or 

OFF

).

C21

and 

C22

: actual status of circuit 2 (

ON

 or 

OFF

).

When the unit is on and a circuit is 

OFF

, the following status

information may appear.

SAFETY ACT.

:  one of the circuit safety devices is activated

(refer to 

"Troubleshooting" on page 20

).

FREEZEUP DIS

: the compressor is disabled by the freeze-up

disable function.

FREEZEUP PR

: freeze-up prevention is active.

DEFROST BUSY

: defrost is active on this circuit.

COMP PR

: compressor protection function is active.

HP SETBACK

: high pressure setback is active.

MIN.RUN.TIM

:  minimum running time of the compressor is

active.

LIMIT

: the compressor is limited by the limitation function.

STANDBY DICN

:  when in a DICN configuration, the unit is in

stand by mode because there is sufficient current capacity to
maintain set point.

UNIT OFF

: the unit is switched off.

AREC INLET

:  the compressor will not start up when the inlet

water temperature has not risen enough compared to previous
switch off of the compressor.

FREE COOLING

: free cooling mode is active

TIMER BUSY

: the actual value of one of the compressor timers

is not zero (refer to 

"Timers menu 

Ó

" on page 13

).

PUMPLEAD TIM

: the compressor will wait to start up for as long

as the pump lead timer is counting down.

NO FLOW

: there is no flow after pumplead, the unit is in stand-by

mode.

NO PRIORITY

: This compressor will not start up because it has

no priority. Refer to 

"Defining the lead-lag settings" on page 16

 for

adjusting the priority.

CAN STARTUP

:  the circuit is ready to start up when extra

cooling or heating load is needed.

When none of the above mentioned messages appears, no
special functions are active and the compressor is running.

The preceding messages are written down in order of priority.
The 

UNIT CAPACITY

 is written down on the bottom of the first

screen.

7

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

EXTRA READOUT

  screens of the readout menu are

providing the following information:

CURRENT

:  actual current, measured in Ampere (

A

) (only when

OP57 is installed)

VOLTAGE

: actual voltage (

V

) (only when OP57 is installed)

RH11

/

12

/

21

/

22

: actual running hours (

h

)

C11

/

12

/

21

/

22C

: actual running hours in cooling mode

C11

/

12

/

21

/

22H

: actual running hours in heating mode

CS11

/

12

/

21

/

22

: number of compressor start-ups

RHP1

/

2

: actual running hours (

h

) of the pump 1 or 2

8

Press the 

 key to return to the other readout menus.

Selecting cooling or heating operation

The "cooling/heating" menu allows the user to set the unit in cooling,
or heating operation.

The 

COOLING/HEATING

 menu provides information concerning the

selected mode:

COOLING

: cooling mode. The two cooling setpoints for both inlet

water temperature control and outlet water temperature control
can be used.

HEATING

:  heating mode. The two heating setpoints for both

inlet water temperature control and outlet water temperature
control can be used.

To define cooling/heating operation, proceed as follows:

1

Enter the cooling/heating menu. Refer to the chapter 

"How to

enter a menu" on page 8

.

If the controller is already in the cooling/heating menu, position
the cursor in the upper left corner of the actual screen using the

K

 key.

2

Position the cursor behind 

MODE

 using the 

K

 key.

3

Select the appropriate setting using the 

h

 and 

g

 keys.

4

Press 

K

 to confirm the selection.

The cursor returns to the upper left corner of the screen.

NOTE

For a DICN system, the 

INLET WATER

 and 

OUTLET

WATER

  values are the values of the individual units,

not of the system. Temperatures of the system can be
consulted in the first screen of the network menu.

NOTE

When 

COOLING

 or 

HEATING

 is selected on a unit in a

DICN system, this mode is transferred to all other
units.

NOTE

When a remote cool/heat switch is configured, the
cooling/heating mode is based on the switch status. In
this case the cooling mode or heating mode can not be
modified in the cooling/heating menu.

Содержание EWYQ080DAYN

Страница 1: ...OPERATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start...

Страница 3: ...p 15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Maximum running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency...

Страница 4: ...r supply intake 32 Liquid receiver 2 Condenser in cooling mode or evaporator in heating mode 17 Switchbox 33 Pump optional 18 Digital display controller behind service panel 34 Buffer tank optional 3...

Страница 5: ...nters the evaporator via an expansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p M12C M11C M15F M13F M14F R14T B1PL...

Страница 6: ...al The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phase protector general safety device The reverse phase protectors prevent the unit from...

Страница 7: ...ercurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWYQ080 100 and EWYQ180 250 K15S Fan overcurrent relay for circuit 1 only for EWYQ080 100 and EWYQ180 250 K16F Fancontactor for c...

Страница 8: ...ally installed protection devices are of the size and type specified in the installation manual Make sure that neither a fuse nor a protection device has been bypassed 3 Earth wiring Make sure that th...

Страница 9: ...k oriented modular structure Apart from the first section which gives a brief description of the controller itself each section or subsection deals with a specific task you can perform with the unit D...

Страница 10: ...n a unit with status NORMAL or STANDBY all other units with status NORMAL or STANDBY will be ON or OFF If the key is pressed on a unit with status DISCONNECT ON OFF only this unit will be ON or OFF Co...

Страница 11: ...ter temperature has not risen enough compared to previous switch off of the compressor FREE COOLING free cooling mode is active TIMER BUSY the actual value of one of the compressor timers is not zero...

Страница 12: ...work safety occurs in a DICN configuration the slaves not detected by the network will function as stand alone units If a slave unit can not be found by the network the red light inside the key of the...

Страница 13: ...l informa tion about the current Ampere and voltage of the unit _v 0U4 013 6 11 12 H 012 0 21 22 H _ COOL INLSP1 012 0 INLET WATER 013 6 OUTLET WATER 007 0 AMBIENT 006 5 _ C1 TEMP READOUT C11 DISCHARG...

Страница 14: ...IC READOUT YES _v MANUAL DEFROST UNIT DEFROST OFF CIR1 DEFROST OFF CIR2 DEFROST OFF _ DEFROST MIN TIME BETWEEN DEFROST NORMAL ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the gene...

Страница 15: ...2 C12RH 00000hCS 00000 C12C 00000h H 00000h _ UNIT HISTORY 002 C21RH 00000hCS 00000 C21C 00000h H 00000h _ UNIT HISTORY 002 C22RH 00000hCS 00000 C22C 00000h H 00000h _ UNIT HISTORY 002 AI1 NONE AI2 NO...

Страница 16: ...control mode The unit is equipped with a thermostat which controls the cooling or heating capacity of the unit Select the appropriate mode MANUAL CONTROL manual control mode the operator controls the...

Страница 17: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 18: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 19: ...counting when the compressor circuit 1 2 has started During the countdown the compressor cannot be restarted MINIMUM RUNNING TIME M RT 120 sec starts counting when the compressor has started During th...

Страница 20: ...h REMOTE COOL HEAT indicates the position of the remote cool heat switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOISE indicates the status...

Страница 21: ...next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain t...

Страница 22: ...y devices are activated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety device...

Страница 23: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 24: ...essary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRECTIVE ACTION The sensor is broken or not correctly wired Check if the wiring is acco...

Страница 25: ...er quality refer to the installation manual of the unit for specifications of the water quality Water filters Make sure to clean the water filter in front of the evaporator water inlet once every 4 mo...

Страница 26: ...s load up requests of maximum 2 compressors at a time A Load up request of 1 compressor B No action C Load down request of 1 compressor D Inlet setpoint E Outlet setpoint INLET CONTROL Default value L...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...FO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PASSWORD 0000 TO LOGIN ENTER PASSWORD PASSWORD 0000 TO LOGIN _ COOLING HEATING MODE COOLING STARTUP BUSY READOUT MENU SETPOINTS...

Страница 29: ...ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1 OFF _ UNIT HISTORY 002 HP2 019 0b 050 8 LP2 004 4...

Страница 30: ...4PW35558 1B Copyright Daikin...

Отзывы: