EWYD_BZ 

 

WORKING WITH THIS UNIT 

5.1  Controller purpose 

Then system will control the evaporator leaving water temperature to keep it at a setpoint value.  
 
The system operates to optimize components performances from the point of view of their efficiency and of their duration. 
 
The system assures a safe operation of the unit and of all components and prevents dangerous situations.  

5.2  Unit enabling 

The control allows different ways to enable/disable the unit: 
 

 

Keypad: Enter key on the keypad allows to switch between  “Power  OFF” mode and  “Unit On” if other signals 
allows this state 

 

 

Local Switch: when the digital input “Unit On/Off” is open the unit is in “Local switch Off”; when the digital input 
“Unit On/Off” is closed the unit may be in “Unit On” or “Remote switch Off” on the basis of the “Remote On/Off “ 
digital input 

 

 

Remote Switch: when the local switch is On (“Unit On/Off” digital input closed) if the digital input “Remote On/Off 
“ is closed the unit is in “Unit On”, when digital input “Remote On/Off “ is open the unit is in “Remote switch Off”  

 

 

Network: a BAS or a Monitoring system may send an On/Off signal trough the serial line connection to put the 
unit on or in “Rem. Comm. Off” 

 

 

Time schedule : a timetable allows to program “Time Schedule  Off” on a  week base; several holiday days are 
include. 

 

 

Ambient LockOut : the unit is not enabled to operate unless the ambient temperature is higher than an adjustable 
value (default 15.0°C (59.0 F) ) 

 

To be in “Unit On” all the allowed signals must enable the unit. 

5.3  Unit modes 

The unit is able to work in the following modes: 

 

Cooling

When this mode is selected the control will operate to cool the evaporator water; the setpoint range is   +4.0 

 +14.0 °C, (39.2 

 57.2 F) a freeze alarm setpoint is  set to 2 °C  (34.6  F) (adjustable by the operator in the range +1 

 +3 °C (33.8 

 37.4 F) ) and a freeze prevent setpoint is  set to 3 °C (37.4 F) (adjustable by the operator in the range: 

“freeze alarm setpoint” + 1 

 

+3 °C (“freeze alarm setpoint” + 1.8 F 

 37.4 F) ). 

 

Cooling/Glyco

When this mode is selected the control will operate to cool the evaporator water; the setpoint range 

are  -8°C 

 +14.0°C (17.6 

 57.2 F) , a freeze alarm setpoint are  set to 

–10 °C (14.0 F)  (adjustable by the operator 

in the range 

–12 °C 

 -9°C (10.4 

 15.8 F) ) and a freeze prevent setpoint are  set to 

–9 °C (15.8 F) (adjustable by the 

operator in the range “freeze alarm setpoint” + 1°C 

 -

9 °C (“freeze alarm setpoint” + 1.8 F 

 15.8 F)) 

 

Ice. 

When this mode is selected the control will operate to cool the evaporator water; the setpoint range are   -8°C 

 

+14.0°C (17.6 

 57.2 F) , a freeze alarm setpoint are  set to 

–10 °C (14.0 F)  (adjustable by the operator in the range 

–12 °C 

 -9°C (10.4 

 15.8 F) ) and a freeze prevent setpoint are  set to 

–9 °C (15.8 F) (adjustable by the operator in 

the range “freeze alarm setpoint” + 1°C 

 -

9 °C (“freeze alarm setpoint” + 1.8 F 

 15.8 F)). While working in ice mode 

compressors are not be allowed to unload but are stopped using a step procedure (se § 5.5.1) 

 

Heating

When this mode is selected the control will operate to heat the evaporator water; the setpoint range is  +30 

 +45°C (86 

 113°C), a hot water alarm setpoint are  set to 50°C (adjustable by the operator in the range +46 

 +55°C 

(114.8 

 131 F) ) and a hot prevent setpoint are  set to 48°C (118.4 F) (adjustable by the operator in the range  +46°C 

 

“hot water alarm setpoint” + 1°C (114.8 F 

 

“hot water alarm setpoint” + 1.8 F)). 

 

C Heat Recovery

Setpoints and freeze protection are  managed as described in the cooling mode; in addition 

the control will enable the heat recovery input and outputs foreseen on the expansion #2  

 

Cooling/ Heat Recovery. 

Setpoints and freeze protection are  managed as described in the cooling/glycol 

mode; in addition the control will enable the heat recovery input and outputs foreseen on the expansion #2. 

 

Ice + Heat Recovery

Setpoints and freeze  protection are managed as described in the ice mode; in addition the 

control will enable the heat recovery input and outputs foreseen on the expansion #2. 

Содержание EWYD-BZ

Страница 1: ...parteinvert Air Cooled chiller heat pump with screw compressors EWYD_BZ REV 01 Date November 2020 Supersedes D EOMCP00104 14EN Operating Manual D EOMCP00104 14_01EN...

Страница 2: ...n 19 5 8 Compressors startup procedure 19 5 9 Fan pre starting in heating mode 19 5 10 Prepurge procedure with electronic expansion 19 5 11 Prepurge procedure with thermostatic expansion 19 5 12 Oil h...

Страница 3: ...n heating mode 26 5 24 Other functions 26 5 24 1 Hot Chilled Water Start 26 5 24 2 Fan Silent Mode 26 5 25 Unit and compressors status 26 5 26 Start up sequence 28 5 26 1 Unit start up and shut down f...

Страница 4: ...it Do not service or operate on the unit without having switched off the main switch 1 2 Before switching the unit Before switching on the unit read the following recommendations When all the operatio...

Страница 5: ...r Cooled CP Condensing Pressure CSRT Condensing Saturated Refrigerant Temperature DSH Discharge Superheat DT Discharge Temperature E M Energy Meter Module EEWT Evaporator Entering Water Temperature EL...

Страница 6: ...pCOe Water pump control N pCOe EXP 4 pCOe Additional fan steps for compressors 1 2 or for compressors 3 N EEXV driver 1 EVD Evolution Electronic expansion valve control for compressor 1 Y EEXV driver...

Страница 7: ...Operating Manual D EOMCP00104 14_01EN EWYD_BZ 7 35 3 2 Main components Unit controller EVD Evolution Electronic Expansion Valves controller...

Страница 8: ...3 3 Components operating limits Component Temperature C r H non condensing pCO5 built in display 20 60 90 pCO5 40 70 90 EVD Evolution N A 90 pCOe 10 60 90 EVD Evolution Electronic Expansion Valves co...

Страница 9: ...ettings submenu Down Maint submenu Built In PGD navigation Entering any other section different menus or mask loops are shown From every loop with or key it is possible to access the father menu and s...

Страница 10: ...beginning from the main menu is shown Masks loops of the same group of parameters can be accessed using left and right arrows creating also horizontal loops Parameters within a same horizontal loop co...

Страница 11: ...Pressure bar psi Temperature C F Time sec sec As far as pressure is concerning the interface shows if shown data are gauge or absolute using the postfix g or a respectively 4 3 Default passwords Sever...

Страница 12: ...is set to 3 C 37 4 F adjustable by the operator in the range freeze alarm setpoint 1 3 C freeze alarm setpoint 1 8 F 37 4 F Cooling Glyco When this mode is selected the control will operate to cool t...

Страница 13: ...tpoint reset methods are available to modify the local or double setpoint None local or double setpoint are used on the base of the double setpoint digital input This is called base setpoint 4 20mA ba...

Страница 14: ...pressor remains in Automatic and must be re switched to Manual by the operator if required Compressors in manual mode are automatically switched in automatic mode at their shutdown The compressor load...

Страница 15: ...f the last compressor is allowed only if the absolute value of the difference between the measured temperature and the setpoint exceeds a Shutdown T value A FILO First In Last Off logic is adopted The...

Страница 16: ...tion Band Max 0 Max PD controller proportional action 5 5 2 Manual Control The control will apply a fixed duration pulse the magnitude is the pulse duration set in the automatic control for each manua...

Страница 17: ...ixed at 75 Unload up to 50 Start Off 12b SetP RDT T or T SetP RDT Fixed at 75 Fixed at 75 Start Off 13 Fixed at 75 Fixed at 75 or 50 Load up to 50 Off 14 if lag1 at 50 Fixed at 75 Load up to 75 Fixed...

Страница 18: ...b SetP RDT T or T SetP RDT Fixed at 75 Fixed at 75 Fixed at 10 if lag2 at 75 Fixed at 75 Fixed at 75 Fixed at 11 Fixed at 75 Unload up to 50 Fixed at 50 12 Fixed at 75 Fixed at 50 Fixed at 25 13 If T...

Страница 19: ...ed and its loading will not be enabled up to the pressure ratio exceeds a set value default equal to 2 5 8 Compressors startup procedure Before to start compressors the unloading solenoid valve is ene...

Страница 20: ...is reached a Low Ambient Start Up low pressure alarm is issued At the end of the low OAT start the evaporator pressure is checked If the pressure is greater than or equal to the evaporator pressure s...

Страница 21: ...eat Defrost procedure will never be executed if Ta 7 C adjustable under maintenance password Defrost procedure will never be executed if Ts 0 C adjustable under maintenance password During defrost the...

Страница 22: ...very loop it will disable all recovery circuits at the same time if the heat recovery water temperature rises above an adjustable threshold default 50 0 C A three way valve is used to increase recover...

Страница 23: ...o pumps are selected the system will automatically start the pump with lower operating hours each time a pump has to be started A fixed starting sequence may be set A pump is started when the unit is...

Страница 24: ...e value 25 sec At the same manner a stage down is executed the previous stage is activated if the pressure ratio falls below the target setpoint by an amount equal to a stage down dead band depending...

Страница 25: ...when condensing temperature is within the deadband or a new stage is activated Each fan stage will have its own adjustable stage up default 0 2 and stage down default 0 2 deadband 5 23 1 2 3 Control o...

Страница 26: ...e of 10 0 C 50 0F If the condensation control is either speedtroll or fantroll each step is activated after a fixed delay of 6 seconds The control is released to automatic control if the outside ambie...

Страница 27: ...off 3 Off Ready 4 Off Ready 5 Off Ready 6 Off Ready 7 Off Switch Compressor is off from switch 8 Auto Automatic compressor load management 9 Manual Manual compressor load management 10 Oil Heating Co...

Страница 28: ...requires unit unloading New Compressor start required see loading table Yes No New Compressors selection Compressors loading Compressors standby Compressor line contactor closing Transition confirmati...

Страница 29: ...Operating Manual D EOMCP00104 14_01EN EWYD_BZ 29 35 Unit Stop Compressors shutdown procedure Evap flow switch open within timer expiration Yes Unit Trip No Unit Off...

Страница 30: ...rt No HR Trip Yes HR temperature control stabilitation HR circuits activation enabled Control requires loading Control requires standby Control requires unloading Loading interstage timer expired PID...

Страница 31: ...Operating Manual D EOMCP00104 14_01EN EWYD_BZ 31 35 Heat Recovery Stop Circuits deactivation procedure Evap flow switch open within timer expiration Haet Recovery Off No HR Trip Yes 3Way valve opening...

Страница 32: ...ressors trip Compressor trips are caused by Mechanical High pressure A High pressure switch alarm will trip the compressor as soon as the high pressure switch opens A manual reset of the alarm is requ...

Страница 33: ...than 10 seconds from compressor start A manual reset of the alarm are required to restart the unit Compressor overload or motor protection A Compressor overload alarm will trip the compressor if the...

Страница 34: ...e alarm on circuit 1 27 Expansion Error Expansion boards error 28 29 EXV Driver Alarm 1 EXV Driver 1 Alarm 30 EXV Driver Alarm 2 EXV Driver 2 Alarm 31 Restart after PW Loss Restart after power loss 32...

Страница 35: ...cular purpose of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin App...