EWWQ090G ÷ EWWQ720L - R410a - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410a - Condenser less
EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers
Water cooled scroll chillers & heat pump
Operation
Manual
EWWQ - EWLQ - EWHQ
Water cooled scroll chiller &heat
pump
D-EOMWC01203-15EN
Operation Manual
51
-
High Pressure: when unit works as chiller or as heat pump with water inversion
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff CndFlwAlm
String in the alarm log:
UnitOff CndFlwAlm
String in the alarm snapshot:
UnitOff CndFlw Alm
No condenser water flow sensed
continuously or water flow too low.
Check the condenser water pump
filler and the water circuit for
obstructions.
Check the condenser flow switch
calibration and adapt to minimum
water flow.
Check if condenser pump impeller
can rotate freely and it has no
damages.
Check condenser pumps protection
devices
(circuit
breakers,
fuses,
inverters, etc.)
Check
condenser
flow
switch
connections.
6.1.3.7 Evaporator Water Freeze Protect alarm
This alarm is generated to indicate that the evaporator (entering or leaving) water temperature has
dropped below a safety limit.
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
String in the alarm list:
+UnitOff EvpFreezeAlm
String in the alarm log:
UnitOff EvpFreezeAlm
String in the alarm snapshot:
UnitOff EvpFreeze Alm
Water flow too low.
Increase the water flow.
Inlet temperature to the evaporator is
too low.
Increase the inlet water temperature.
Flow switch is not working or no water
flow.
Check the flow switch and the water
pump.
Refrigerant temperature become too
low (< -0.6°C).
Check the water flow and filter. No
good heat exchange conditions into
the evaporator.
Sensors
temperature
readings
(entering or leaving) are not properly
calibrated
Check the water temperatures with a
proper instrument and adjust the
sensor offsets
6.1.3.8 Condenser Water Freeze Protect alarm
This alarm is generated to indicate that the condenser (entering or leaving) water temperature has
dropped below a safety limit.
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
String in the alarm list:
+UnitOff CondFreezeAlm
String in the alarm log:
UnitOff CondFreezeAlm
String in the alarm snapshot:
UnitOff CondFreeze Alm
Water flow too low.
Increase the water flow.
Inlet temperature to the condenser is
too low.
Increase the inlet water temperature.
Flow switch is not working or no water
flow.
Check the flow switch and the water
pump.
Refrigerant temperature become too
low (< -0.6°C).
Check the water flow and filter. No
good heat exchange condition into the
evaporator.
Sensors
temperature
readings
(entering or leaving) are not properly
calibrated
Check the water temperatures with a
proper instrument and adjust the
sensor offsets