EWWQ090G ÷ EWWQ720L - R410a - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410a - Condenser less
EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers
Water cooled scroll chillers & heat pump
Operation
Manual
EWWQ - EWLQ - EWHQ
Water cooled scroll chiller &heat
pump
D-EOMWC01203-15EN
Operation Manual
29
Heat/Cool w/Glycol
Heat/Ice w/Glycol
Pursuit
Test
4.7 Timers
This page indicates the remaining cycle timers for each compressor. When the cycle timers are
active any new start of a compressor is inhibited.
Setpoint/Sub-Menu
Default
Range
Description
Comp 1=
0s
Comp 2=
0s
Comp 3=
0s
Comp 4=
0s
Clear Cycle Tmrs
Off
Off,On
Clear Cycle Timers
Stg Up Dly Rem=
Stg Dn Dly Rem=
Clr Stg Delays=
Off
Off,On
Clear Stages Delays
Ice Cycle Dly Rem
Clear Ice Dly=
Off
Off,On
Cleat Ice Delay
4.8 Alarms
This link jumps to the Alarm page. Each of the items represents a link to a page with different
information. The information shown depends on the abnormal operating condition that caused the
activation of unit, circuit or compressor safeties. A detailed description of the alarms and how to
handle will be discussed in the section Troubleshooting this chiller.
Setpoint/Sub-Menu
Default
Description
Alarm Active
List of the active alarms
Alarm Log
History of all the alarms and acknowledges
Event Log
List of the events
Alarm Snapshot
List of alarm snapshots with all the relevant data recorded at time the alarm occurred.
4.9 Commission Unit
Setpoint/Sub-Menu
Default
Range
Description
Configure Unit
See section 4.9.1
Alarm Limits
See Section 4.9.2
Calibrate Unit Sensors
See section 4.9.3
Calibrate Circuit Sensors
See section 4.9.4
Unit Manual Control
See section 4.9.5
Circuit 1 Manual Control
See section 4.9.6
Circuit 2 Manual Contorl
Scheduled Maintenance
See section 4.9.7
4.9.1 Configure Unit
This page resumes all the specific settings for this unit like unit type, number of circuits, type of
condensing control, etc.. Part of these settings cannot be adjusted and are supposed to be set
during the manufacturing or commissioning of this unit. The modification of each parameter in this
menu requires that the unit switch is set to 0.
Setpoint/Sub-
Menu
Default
Range
Description
Apply Changes=
No
No, Yes
Type yes after changes
Unit Type=
EWWD
EWWD, EWLD
Select the unit type, chiller (EWWD) or condenser less
(EWLD)
Number Of Cir=
1
1,2
Number of circuit of the chiller
Inversion Type
No
No, Water, Gas
Type of inversion in heat pump mode.
Cond Ctrl Var=
No
No, Pressure, Cond In, Cond Out
Enabling of the condensing control
Cond Ctrl Dev=
None
None, Valve, VFD
Select device type used for condensing control