EWWQ090G ÷ EWWQ720L - R410a - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410a - Condenser less
EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers
Water cooled scroll chillers & heat pump
Operation
Manual
Operation Manual
28
EWWQ - EWLQ - EWHQ
Water colled scroll chiller &heat pump
D-EOMWC01203-15EN
Output=
-
-
Actual condensing control output
Max Output=
100.0%
50…100%
Maximum condensing control output
Min Output
0.0%
0…50%
Minimum condensing control output
4.3.1.3 EXV
This page resumes all the relevant information about the status of the EXV logic. For more details
about this parameters and the control logic of the EXV refer to section 5.5.
Setpoint/Sub-Menu
Default
Range
Description
EXV State=
Closed
Closed, Pressure, Superheat
Suction SH=
-
Suction Superheat
Evap Pressure
-
Evaporating pressure
Act Position=
-
Expansion valve opening
Cool SSH Target=
6.5dK
4.4
…30.0dK
Cool Suction Superheat setpoint
Heat SSH Target=
6.5dK
2.5…30.0dK
Heat Suction Superheat setpoint
Max Op Pressure=
900.0 kPa
890.0…1172.2kPa Maximum operating pressure
Pre Open Time
5.0sec
0…100sec
Preopening Time
Pre Open %=
20%
0…100%
Valve opening percentage in Preopening state
Start Time=
30sec
0…100sec
Starting Time
Start %=
35%
0…100%
Valve opening percentage in Starting state
4.4 Tmp Setpoints
This page allows to set the water temperature setpoints in the several modes. For more details
refer to the section 5.1.3.
Setpoint/Sub-Menu
Default
Range
Description
Cool LWT 1=
7.0°C
4.0…15.0°C (cool mode)
-
8.0…15.0°C (cool w/ glycol mode)
Primary cooling setpoint
Cool LWT 2=
7.0°C
4.0…15.0°C (cool mode)
-
8.0…15.0°C (cool w/ glycol mode)
Secondary cooling setpoint (see 3.6.3)
Ice LWT=
4.0°C
-
10.0…4.0°C
Ice setpoint (ice banking with on/off mode)
Heat LWT 1=
45.0°C
25.0…55.0°C
Primary heating setpoint
Heat LWT 2=
45.0°C
25.0…55.0°C
Secondary heating setpoint
4.5 Temperatures
This page shows all water temperatures, evaporator and condenser delta temperature between
inlet and outlet.
Setpoint/Sub-Menu
Default
Range
Description
Evap LWT=
-
-
Evaporator leaving water temperature
Evap EWT=
-
-
Evaporator entering water temperature
Cond LWT=
-
-
Condenser leaving water temperature
Cond EWT=
-
-
Condenser entering water temperatue
Evap Delta T=
-
-
Evaporator delta temperature
Cond Delta T=
-
-
Condenser delta temperature
Evap LWT Slope=
-
-
Evaporator leaving water temperature rate of change
Cond LWT Slope=
-
-
Condenser leaving water temperature rate of change
4.6 Available Modes
This page allows to set the operating mode of the unit. For more details about these parameters
and the available modes of the unit refer to section 5.1.2.
Setpoint/Sub-Menu
Default
Range
Description
Modes
Cool
Cool
Cool w/Glycol
Cool/Ice w/Glycol
Ice
Heat/Cool