EWWQ090G ÷ EWWQ720L - R410a - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410a - Condenser less
EWHQ100G ÷ EWHQ400G - R410a - Heat pump scroll chillers
Water cooled scroll chillers & heat pump
Operation
Manual
EWWQ - EWLQ - EWHQ
Water cooled scroll chiller &heat
pump
D-EOMWC01203-15EN
Operation Manual
23
4 Menu Structure
All settings are divided in different menus. Each menu collects in a single page other sub-menus,
settings or data related to a specific function (for example Power Conservation or Setup) or entity
(for example Unit or Circuit). In any of the following pages a grey box will indicate changeable
values and the defaults.
4.1 Main Menu
Setpoint/Sub-Menu
Default
Range
Description
Enter Password
-
Submenu to activate access levels
View/Set Unit
-
Submenu for unit data and settings
View/Set Circuit
-
Submenu for circuit data and settings
Unit Status=
Off: Unit Loc/Rem Sw
Auto
Auto: Mtr Prot Delay
Off:
Ice Mode Tmr
Off:
All Cir Disabled
Off:
Unit Alarm
Off:
Keypad Disable
Off:
BAS Disable
Off:
Unit Loc/Rem Sw
Off:
Test Mode
Auto:
Wait For Load
Auto:
Evap Recirc
Auto:
Wait For Flow
Auto:
Pumpdn
Auto: Max Pull Limited
Auto:
Unit Cap Limit
Off: Cfg Chg, Rst Ctrlr
Status of the Unit
Active Setpt=
7.0°C
-
Active setpoint and link to the Setpoint
page
Evap LWT=
-273.1°C
-
Evaporator leaving water temperature and
link to the Temperatures page
Cond LWT=
-273.1°C
-
Condenser leaving water temperature and
link to the Temperatures page
Unit Capacity=
0.0%
-
Unit staging
Chiller Enable=
Enable
Enable-Disable
Chiller operation enable/disable setting
Unit Mode=
Cool
-
Actual unit mode and link to unit mode
page
Timers
-
Submenu
compressors
and
thermoregulation safety timers
Alarms
-
Submenu for alarms; same function as Bell
Button
Commission Unit
-
Submenu for the chiller configuration
About Chiller
-
Application Info submenu