3.7 Software Update procedure
UC can be updated by using an SD card and an appropriate pin.
Actual BSP and software version installed on UC can be checked in the About Chiller page.
SD card has to be FAT32 formatted before any update process can be started. Supported SD
types are:
-
SD standard
-
High speed SD
-
SDHC
The following SD cards have also been tested and found operational:
-
1 GByte SD V1.0 (Inmac)
-
2 GByte SD V2.0 SpeedClass 2 (SanDisk),
-
4 GByte SDHC V2.0 SpeedClass 6 (Hama High Speed Pro),
-
4 GByte SDHC V2.0 SpeedClass 4 (SanDisk Ultra II),
-
8 GByte micro SDHC SpeedClass 4 (Kingston)
In case an update is received all the files included in the archive are to be saved in the SD card
with their original name. The standard software pack is composed with 6 files:
1. BSP file (operative system of the UC),
2. Code file,
3. HMI file,
4. OBH file (multilingual and protocol support),
5. HMI for Web (web interface),
6. Cloud file.
The software for this specific range of units cannot be used with the Large UCs (POL687.xx/MCQ)
used on other products. In case of doubts, please contact your Daikin Service reference.