Operation manual

7

EWWP045~06 ECB1~3MUW

Packaged water-cooled water chillers

4PW30041-1A

Adjusting the heating temperature setpoint

In addition to the cooling setpoint, the 16~24Hp units enable
definition of a temperature setpoints for heating operation.  The
default, limit and step values for the heating setpoint are:

Default value

30

°C

Limit values

15

 to  

50

 °C

Step value

from 

15

.

0

 to 

19

.

9

°C

0

.

1

°C

from 

20

 to 

50

°C

1

°C

To adjust the heating temperature setpoint, proceed as follows:

1

Press the 

R

 key for approximately 5 seconds to enter the list of

direct parameters.

The direct parameter code 

r1

 defining the cooling temperature

setpoint appears on the display.

2

Press the 

A

 key twice.

The direct parameter code 

r3

 defining the heating temperature

setpoint appears on the display.

3

Press the 

R

 key.

The actual heating temperature setpoint appears on the display.

4

Press the 

A

  or 

Z

  key  to raise, respectively lower the

temperature setting.

5

Press the 

R

 key to return to parameter code 

r3

.

6

To save the adjusted temperature setpoint, press the 

E

 key. To

cancel the modification wait approximately 40 seconds.

In the first case, the controller saves the changes, leaves the list
of direct parameters and returns to normal operation, displaying
the inlet water temperature.
In the second case, the display starts flashing. Approximately
40 

seconds later, the controller leaves the list of direct

parameters without saving the modified parameter. The inlet
water temperature reappears on the display. 

Consulting actual operational information

The actual operational information that can be consulted in the list of
direct parameters consists of:

r6

 : outlet water temperature evaporator,

r8

 : when cooling mode is active: inlet water temperature of the

condenser,
when heating mode is active: inlet water temperature of the
evaporator,

c9

 : total running hours of the compressor1,

ca

 : total running hours of the compressor2,

cv

 : total running hours of the pump.

To consult the actual operational information, proceed as follows:

1

Press the 

R

 key for approximately 5 seconds to enter the list of

direct parameters.

The direct parameter code 

r1

 defining the cooling temperature

setpoint appears on the display.

2

Depending on the information to be consulted, select parameter
code 

r6

r8

c9

ca

 or 

cv

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

  key  to consult the actual value of the selected

parameter.

4

Press the 

R

 key to return to the parameter codes.

5

To  consult other actual operational information, repeat from
instruction 2 onwards.

6

To  return to normal operation, press the 

E

  key or wait

approximately 40 seconds.

In the first case, the controller immediately leaves the list of
direct parameters and returns to normal operation displaying the
inlet water temperature.
In the second case, the display will start flashing. Approximately
40 seconds later, the controller leaves the list of direct para-
meters. The inlet water temperature reappears on the display.

Resetting alarms

When an alarm is detected, the following happens:

the buzzer is activated (if enabled by means of user parameter 

p4

),

the alarm relay is energized,

the display starts flashing, alternately showing the alarm code
and the inlet water temperature.

The following alarm codes may appear on the screen:

a1

: indicates an anti-freeze alarm,

e1

: indicates that the NTC probe used to measure the

evaporator inlet water temperature is defective,

e2

: indicates that the NTC probe used to measure the outlet

water temperature is defective,

e3

: indicates that the NTC probe used to measure the

condenser inlet water temperature is defective,

ee

,

ep

: indicates that the EEPROM on the controller PCB inside the

unit is defective,

ei

,

e0

: indicates that the supply voltage is exceedingly low (

ei

) or

exceedingly high (

e0

). In these cases contact a licensed

electrician,

el

: indicates that the power supply has a "remarkable noise". In

this case contact a licensed electrician,

f l

: indicates that there was no water flow either during the

period of 15 seconds after the pump was started or for 5
seconds while the compressor is active,

h1

: indicates that a high pressure switch, the discharge thermal

protection or the overcurrent protection of the compressor
motor is activated, 

l1

: indicates that the low pressure switch is activated. 

To reset an alarm, proceed as follows:

1

Press the 

O

 key to acknowledge the alarm.

The buzzer is de-activated.

2

Find the cause of shutdown and correct.

Refer to the chapter 

"Troubleshooting" on page 19

.

3

If the alarm codes 

a1

f l

h1

 or 

l1

 appear on the display, reset

the alarm manually by pressing the 

A

  and 

Z

  key

simultaneously for approximately 5 seconds.

In all other cases the alarm is reset automatically.

Once the alarm is reset, the error code no longer appears on the
display. The controller continues its normal operation, displaying
the inlet water temperature.

NOTE

To  reset the timers 

c9

ca

  and 

cv

, refer to chapter

"Resetting warnings" on page 8

.

NOTE

If the alarm codes 

f l

  and 

h1

  are flashing alternately,

the alarm is most probably caused by the reverse
phase protector.

Содержание EWWP045KAW1M

Страница 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Страница 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Страница 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Страница 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Страница 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Страница 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Страница 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Страница 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Страница 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Страница 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Страница 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Страница 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Страница 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Страница 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Страница 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Страница 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Страница 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Страница 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Страница 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Страница 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Страница 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Страница 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Страница 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Страница 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Страница 25: ...NOTES NOTES...

Страница 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30041 1A...

Отзывы: