EWWP014~065KBW1N

Packaged water-cooled water chillers

4PW61660-1A – 04.2012

Operation manual

12

Locking the controller keyboard

Once user parameter 

h09

 is set to 

0

, the following advanced

features can no longer be carried out by means of the controller:

modifying direct and user parameters (parameters can be
displayed but not modified),

resetting the timers.

switching the unit on/off in cooling or heating

When user parameter 

h09

 is set to 

1

, the above-described

advanced features can be carried out using the controller.

To modify user parameter 

h09

 value from 

1

 to 

0

, the standard user

parameter modification procedure can be used with the standard
password "

22

". Refer to 

"How to consult and modify the user

parameters" on page 10

.

To modify user parameter 

h09

 value from 

0

 to 

1

, the user

parameter modification procedure can be used with dedicated
password "

11

". Refer to 

"How to consult and modify the user

parameters" on page 10

.

BMS 

CONNECTION

 

MODBUS

By installing the optional kit address card EKAC10C, you will be able
to communicate with your chiller through a Building Management
System or supervisory system via the Modbus protocol.

General description of Modbus

The address card communicates using the Modbus protocol.

Different parts of the communication network

The communication network consists of two major players:

The Building Management System (BMS) or supervisory
system.

The chiller or multiple chillers.

The BMS or other supervisory system is able to communicate
with the chillers through the address card.
The management of the communication occurs in accordance
with a master-slave structure in polling, where the supervising
BMS is the master and the address cards are the slaves.

The chiller unit can be identified by the supervisor through the
assignment of an address within the Modbus network. The
address of the chiller unit can be programmed during the
configuration of the BMS settings.

The variables database of every chiller with installed address
card is the point of reference for the supplier of the supervisory
system in Modbus to assign a suitable meaning to the variables.
The variables can be read and/or written by the supervisory
system. Whether the variables are read-only or read/write
depends on the connected chiller and/or the application program
being used.
-

If the supervisory system assigns a value to a variable with 
read-only status, the command will not be executed at all.

-

Variables requested by the supervisory system that are not 
available in a chiller with an address card are sent from the 
address card to the supervisory system with zero value. The 
supervisory system will have to manage these properly.

-

In case the supervisory system tries to write a value of a 
parameter that is out of range, the writing will be ignored.

General information about the Modbus protocol

The Modicon Modbus protocol implemented in the address card
complies with the content of the following document:

Modicon Modbus Protocol

Reference Guide

June 1996, PI-MBUS-300 Rev. J

The Modbus protocol implemented is of the RTU (Remote Terminal
Unit) type based on character tranmission times. The configuration
uses the multi-drop feature of RS485. The address sent within the
Modbus packet addresses the chiller unit.

Implemented RS485 communication settings for the Modbus 
protocol

The RS485 communication settings are implemented as follows:

Baud-rate: 9600

Stop bit: 2

Parity: none

Implemented commands for the Modbus protocol

The implemented commands in the program are as listed:

Note that:

Due to the variety of chillers with installed address cards, no
distinction is made between input variables (with read-only
status) and output variables (with read/write status) so that the
knowledge of the database and its management depends on the
part present on the supervisory system.

Due to the general nature of the system, the address card
answers in the same way to various Modbus commands.

Modbus command

Meaning

Notes

01

read coil status

Read digital 
variable(s)

obtains current status (ON/
OFF) of a group of logic coils 
or discrete input

02

read input 
status

Read digital 
variable(s)

obtains current status (ON/
OFF) of a group of logic coils 
or discrete input

03

read holding 
registers

Read analogue 
variable(s)

obtains current binary value 
in one or more holding 
registers

04

read input 
registers

Read analogue 
variable(s)

obtains current binary value 
in one or more holding 
registers

05

force single coil

Write individual 
digital variable(s)

forces single coil to ON or 
OFF status

06

preset single 
register

Write individual 
analogue variable(s)

places a specific binary 
value into a holding register

15

force multiple 
coils

Write series of 
digital variables

forces a series of 
consecutive logic coils to be 
defined to ON or OFF status

16

preset multiple 
registers

Write series of 
analogue variables

places specific binary values 
into a series of consecutive 
holding registers

Содержание EWWP014KBW1N

Страница 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Страница 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Страница 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Страница 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Страница 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Страница 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Страница 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Страница 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Страница 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Страница 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Страница 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Страница 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Страница 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Страница 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Страница 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Страница 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Страница 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...

Страница 18: ......

Страница 19: ......

Страница 20: ...4PW61660 1A 2012 04 Copyright 2010 Daikin...

Отзывы: