Installation manual
2
EWWP014~065KAW1N
Packaged water-cooled water chillers
4PW30038-1
O
PERATION
RANGE
M
AIN
COMPONENTS
(refer to the outlook diagram supplied with the
unit)
1
Compressor
2
Evaporator
3
Condenser
4
Switchbox
5
Chilled water in
6
Chilled water out
7
Condenser water out
8
Condenser water in
9
Evaporator entering water temperature sensor
10 Freeze up sensor
11 Condenser entering water temperature sensor
12 Digital display controller
13 Power supply intake
14 Ball valve (field installed)
15 Water filter (field installed)
16 Air purge valve (field installed)
17 T-joint for air purge (field installed)
18 flowswitch (with T-joint) (field installed)
19 Main switch
S
ELECTION
OF
LOCATION
The units are designed for indoor installation and should be installed
in a location that meets the following requirements:
1
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
2
The space around the unit is adequate for servicing.
3
There is no danger of fire due to leakage of inflammable gas.
4
Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone.
5
Ensure that water cannot cause any damage to the location in
case it drips out of the unit.
I
NSPECTING
AND
HANDLING
THE
UNIT
At delivery, the unit should be checked and any damage should be
reported immediately to the carrier claims agent.
U
NPACKING
AND
PLACING
THE
UNIT
1
Cut the straps and remove the cardboard box from the unit.
2
Cut the straps and remove the cardboard boxes with waterpiping
from the pallet.
3
Remove the four screws fixing the unit to the pallet.
4
Level the unit in both directions.
5
Use four anchor bolts with M8 thread to fix the unit in concrete
(directly or using the floor standing supports).
6
Remove the service front plate.
C
HECKING
THE
WATER
CIRCUIT
The units are equipped with water inlets and water outlets for
connection to a chilled water circuit and to a hot water circuit. These
circuits must be provided by a licensed technician and must comply
with all relevant European and national regulations.
Before continuing the installation of the unit, check the following
points:
■
Additional components not delivered with the unit
1
A circulation pump must be provided in such a way that it dis-
charges the water directly into the heat exchanger.
2
Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.
3
Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.
■
Additional water piping delivered with the unit
All additional water piping must be installed on the system according
to the piping diagram as mentioned in the operation manual. The
flowswitch must be connected as described on the wiring diagram.
See also chapter
LWC
Leaving water temperature condenser
LWE
Leaving water temperature evaporator
a
Glycol
b
Water
Continuous operation range
0
10
20
-10
-5
5
32
0
10
20
30
40
50
60
LWC
55
45
ZL
ZL
ZH
ZH
ZL
ZH
1.5
1.5
1.5
a b
a b
a b
0
10
20
-10
-5
5
32
0
10
20
30
40
50
60
LWC
55
45
ZL
ZL
ZH
ZH
ZL
ZH
-2
-2
-2
a b
a b
a b
EWWP014~035
EWWP045~065
Carton box 1
water piping evaporator
2x Ball valve
1x Water filter
1x Air purge
1x T-joint for air purge
2x Flowswitch pipe
1x Flowswitch
+
1x T-joint
Carton box 2
water piping condenser
2x Ball valve
1x Water filter
1x Air purge
1x T-joint for air purge