Daikin EWWD120MBYNN Скачать руководство пользователя страница 19

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22685-1

Operation manual

18

Symptom 1: The unit does not start, but the ON LED lights up

Symptom 2: The unit does not start, but the ON LED is flashing

Symptom 3: The unit does not start and the ON LED does not light up

3

Symptom 4: One of the circuits does not start up

Symptom 5: One of the following safety devices is activated

5.1

5.2

5.3

5.4

5.5

5.6

5.7

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The temperature setting is not 
correct.

Check the controller setpoint.

The flowstart timer is still running.

The unit will start after approx. 15 
seconds. Make sure that water is 
flowing through the evaporator.

Neither one of the circuits can start 
up.

Refer to Symptom 4: One of the 
circuits does not start up.

Unit is in manual mode (all 
compressors at 0%).

Check on the controller.

Power supply failure.

Check the voltage on the supply 
panel.

Blown fuse or interrupted protection 
device.

Inspect fuses and protection 
devices. Replace by fuses of the 
same size and type (refer to 

"Electrical specifications" on 
page 2

).

Loose connections.

Inspect connections of the field 
wiring and the internal wiring of the 
unit. Tighten all loose connections.

Shorted or broken wires.

Test circuits using a tester and repair 
if necessary.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The remote ON/OFF input is present 
and the remote switch is off.

Put the remote switch on or disable 
the remote ON/OFF input.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

All circuits are in failure mode.

Refer to Symptom 5: One of the 
following safety devices is activated.

One of the following safety devices is 
activated:

• flowswitch (S8L,S9L)
• Emergency stop

Refer to Symptom 5: One of the 
following safety devices is activated.

The ON LED is broken.

Contact your local dealer.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

One of the following safety devices is 
activated:

• Compressor thermal protector (Q*M)
• Overcurrent relay (K*S)
• Discharge thermal protector (S*T)
• Low pressure 
• High pressure switch (S*PH)
• Reverse phase protector (R*P)
• Freeze-up

Check on the controller and refer to 
Symptom 5: One of the following 
safety devices is activated.

The anti-recycling timer is still active.

The circuit can only start up after 
approximately 10 minutes.

The guard timer is still active.

The circuit can only start up after 
approximately 1 minute.

The circuit is limited to 0%.

Check the "enable/disable capacity 
limitation" remote contact.

Symptom 5.1:  Overcurrent relay of compressor

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

Overload of motor.

Reset. If the failure persists, call your 
local dealer.

RESET

Push the blue button on the over-
current relay inside the switch box 
and reset the controller.

Symptom 5.2:  Low pressure 

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to water heat exchanger 
too low.

Increase the water flow.

Shortage of refrigerant.

Check for leaks and refill refrigerant, 
if necessary.

Unit is working out of its operation 
range.

Check the operation conditions of 
the unit.

Inlet temperature to the water heat 
exchanger is too low.

Increase the inlet water temperature.

Dirty evaporator.

Clean the evaporator, or call your 
local dealer

Low pressure safety setting too high.

Refer to the installation manual 
“Customization in the service menu”, 
paragraph “Setting of the minimum 
outlet water temperature” for correct 
values.

flowswitch is not working or no water 
flow.

Check the flowswitch and the water 
pump.

RESET

After pressure rise, this safety resets 
automatically, but the controller still 
needs to be reset.

Symptom 5.3:  High-pressure switch

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to condenser is too low.

Increase the water flow and/or check 
the strainer for clogging.

RESET

After finding the cause, push the 
button on the high-pressure switch 
housing and reset the controller.

Symptom 5.4:  Reverse phase protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Two phases of the power supply are 
connected in the wrong phase 
position.

Invert two phases of the power 
supply (by licensed electrician).

One phase is not connected 
properly.

Check the connection of all phases.

RESET

After inverting two phases or fixing 
the power supply cables properly, 
the protector is reset automatically, 
but the controller still needs to be 
reset.

Symptom 5.5:  Discharge thermal protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit is working outside the operation 
range.

Check the operation condition of the 
unit.

RESET

After temperature decrease, the 
thermal protector resets 
automatically but the controller still 
needs to be reset.

Symptom 5.6:  Flowswitch is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

No water flow.

Check the water pump.

RESET

After finding the cause, the 
flowswitch is reset automatically, but 
the controller still needs to be reset.

Symptom 5.7:  Freeze-up protection is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow too low.

Increase the water flow.

Inlet temperature to the evaporator is 
too low.

Increase the inlet water temperature.

flowswitch is not working or no water 
flow.

Check the flowswitch and the water 
pump.

RESET

After temperature increase the 
freeze-up is reset automatically, but 
the circuit controller needs to be 
reset.

Содержание EWWD120MBYNN

Страница 1: ...OPERATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Страница 2: ...Y KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation m...

Страница 3: ...0 Condensor Type shell tube Qtyxmodel 2x CDEW400 1x CDEW400 1x CDEW450 2x CDEW450 Evaporator Type brased plate heatexchanger Qtyxmodel 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250EQ NP162 2x AC250EQ NP...

Страница 4: ...harge stopvalve 3 Condenser 19 Condensor entering water temperature sensor 4 Switchbox 20 Digital display controller 5 Compressor switchbox 21 Emergency stop 6 Air purge condenser 22 Power supply inta...

Страница 5: ...ion of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection...

Страница 6: ...essure relief safety valve The safety valve is activated when the pressure in the refrigerant circuit becomes too high If this occurs shut down the unit and contact your local dealer High pressure swi...

Страница 7: ...ield wiring Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual according to the wiring...

Страница 8: ...phanumeric display may decrease at low temperatures OPERATION The EWWD120 540 units are equipped with a digital controller offering a user friendly way to set up use and maintain the unit This part of...

Страница 9: ...tialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller does not...

Страница 10: ...frigerant in circuit 1 respectively circuit 2 The first number stands for the pressure in bar the second number stands for the saturation temperature in degrees Celsius low pressure of the refrigerant...

Страница 11: ...rcuits The red LED inside the p key lights up and the buzzer inside the controller is activated When a circuit safety occurs the compressor of the corresponding circuit is shut down The screen of the...

Страница 12: ...n the first screen of the network menu To consult information about the outlet water temperature of the evaporator of circuit 1 and 2 only for EWWD360 540 To consult information about the unit status...

Страница 13: ...information about the network safety which caused the shutdown To consult information about the dual pump wich caused the shutdown To check the time and control mode at the moment of the unit shutdown...

Страница 14: ...evaporator and or condenser entering water temperature to control the capacity of the unit outlet control mode uses the evaporator leaving water temperature to control the capacity of the unit To chec...

Страница 15: ...their setting needs to be reset to See User settings menu on page 11 The screen of the user settings menu allows the user to define the schedule timer settings Each day of the week can be appointed to...

Страница 16: ...rd each time he wants to change the setpoint Defining BMS control allows the user to control the unit from a supervisory system The screen and screen of the service menu have to be used to set BMS par...

Страница 17: ...the latest shutdown To check the safety info and the unit status proceed as follows 1 Enter the Refer to the chapter How to enter a menu on page 8 The controller enters the last screen which contains...

Страница 18: ...e g and h keys 6 Press q to confirm the new password When the new password has been confirmed the controller will ask to enter the new password a second time for safety reasons The cursor is positione...

Страница 19: ...panel or measure the supply voltage Voltage too low Measure the supply voltage Overload of motor Reset If the failure persists call your local dealer RESET Push the blue button on the over current rel...

Страница 20: ...apacity of the unit is too low Call your local dealer Water flow is too high Recalculate the water flow The circuit is limited Check the enable disable capacity limitation remote contact POSSIBLE CAUS...

Страница 21: ...perly and that the earth terminals are tightened Refrigerant circuit Check for leaks inside the unit In case a leak is detected call your local dealer Check the working pressure of the unit Refer to p...

Страница 22: ...to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings in the holiday group All group settings of gro...

Страница 23: ...1 1 q h q q g h h h g h g h g h g h h g h g 2 0 1 1 1 1 g g h g g h g h g h g h g h g h g g h g h g h g h h g g 1 f 3 3 1 4 3 3 1 3 3 3 3 3 3 3 3 3 2 3 3 3 3 g h g h g h q h h g q h g h g h g h g h g...

Страница 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22685 1...

Отзывы: