EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22685-1

Operation manual

16

To check the actual value of the software timers, proceed as follows:

1

Enter the 

 

. (Refer to the chapter 

"How to enter a

menu" on page 8

.)

The controller displays the actual value of the 

 

:  the loadup timer, the loaddown timer, the flowstart

timer, the flowstop timer (when the unit is on and the flowstart
timer has reached zero), the pumplead timer and the pumplag
timer.

2

Press the 

h

 key to check the compressor timers.

The controller shows the actual value of the 

: the guard timers (one per circuit) and the antirecycling

timers (one per circuit).

3

Press the 

h

 key to check the remaining timers.

The controller shows the actual value of the 

 

.

Tasks of the safeties menu

Listing activated safeties and checking the unit status

If the alarm buzzer is activated and the user presses the 

p

 key, the

controller automatically enters the safeties menu.

The controller will enter the 

 

 screen of the safeties

menu when a unit safety was the cause of shutdown.

The controller will enter the 

 

 or 

  

screen of the safeties menu when a safety of the circuit was
activated.

For a DICN system, the controller can also show: 

   

. This occurs when the wrong

number of slave units is defined (refer to 

"Defining the network

settings" on page 15

) or when a slave unit is missing (because

of bad connection or power supply failure).
Make sure to define the correct number of slave units and to
make correct connections.

When the unit is configured with a dual evaporator pump, the
controller will enter the 

   

  screen of the

safeties menu when a safety on the pump was the cause of
shutdown.

1

Press the 

p

 key when the alarm buzzer is activated.

The appropriate safety screen with the basic information
appears. Press the 

q

 key to see the detailed information. These

screens provide information about the unit status at the moment
of shutdown (see 

"Safeties menu" on page 12

).

2

If more than one kind of safety is active (indicated by means of

W

X

 or 

C

), use the 

and

 h

 keys to consult them.

Tasks of the history menu

Checking the safety info and the unit status after a reset

The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the circuit.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest shutdown.

To check the safety info and the unit status, proceed as follows:

1

Enter the 

 

. (Refer to the chapter 

"How to enter a

menu" on page 8

.)

The controller enters the last 

  screen which contains

basic information of the moment of this shutdown.

2

Press the 

and

 h

 keys to consult the other present 

screens.

3

Press the 

q

 key to see the detailed information.

Tasks of the info menu

Consulting additional unit information

1

Enter the 

  

through the main menu. (Refer to the

chapter 

"How to enter a menu" on page 8

).

The controller enters the 

 

  screen which

contains the following information: the time and date.

2

Press 

h

 to consult the first 

 

 screen. 

This screen contains information about the unit name and the
refrigerant used.

3

Press 

h

 to consult the next 

 

 screen.

This screen contains information about the controller's software
version.

4

Press 

h

 to consult the 

 

 screen.

This screen contains information about the PCB.

Tasks of the input/output menu

Checking the status of the inputs and outputs

The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.

The locked digital inputs are:

 

:  whether the emergency button has been

pressed.

 

: indicates the status of the flowswitch: activated or

deactivated.

   

: indicates the actual status of this

safety.

   

:  indicates the actual status of

this safety.

   

: indicates the actual status

of this safety.

 

: indicates the actual status of this safety.

   

:  indicates the actual

status of this safety.

   

: indicates the actual

status of this safety.

The changeable digital inputs are:

   #%

:  indicates the position of the "enable/

disable capacity limitation" switch.

 

:  indicates the position of the remote dual

setpoint switch: setpoint 1 or setpoint 2.

 

: indicates the position of the remote on/off switch.

: indicates the position of the connected switch.

The locked relay outputs are:

 

: indicates whether circuit 1/2 is on/off.

 

:  indicates whether circuit 1/2 is in

starmode or not.

   

:  indicates whether circuit 1/2 is in

deltamode or not.

  +

: indicates if the 12% capacity valve of circuit 1/2

is activated.

 

: indicates if the UP of the capacity control motor of

circuit 1/2 is activated.

 

:  indicates if the DWN of the capacity control

motor of circuit 1/2 is activated.

 

: indicates the FEEDBACK of the potentiometer

of circuit 1/2 (

).

: indicates the status of this voltage free contact.

It is activated if the pump should be ON.

 

: indicates the status of this voltage free contact.  It

is activated if there is any alarm on the unit.

NOTE

You can check the "found" slave units in the 2nd
screen of the network menu.

Содержание EWWD120MBYNN

Страница 1: ...OPERATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Страница 2: ...Y KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation m...

Страница 3: ...0 Condensor Type shell tube Qtyxmodel 2x CDEW400 1x CDEW400 1x CDEW450 2x CDEW450 Evaporator Type brased plate heatexchanger Qtyxmodel 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250EQ NP162 2x AC250EQ NP...

Страница 4: ...harge stopvalve 3 Condenser 19 Condensor entering water temperature sensor 4 Switchbox 20 Digital display controller 5 Compressor switchbox 21 Emergency stop 6 Air purge condenser 22 Power supply inta...

Страница 5: ...ion of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water in outlet connection...

Страница 6: ...essure relief safety valve The safety valve is activated when the pressure in the refrigerant circuit becomes too high If this occurs shut down the unit and contact your local dealer High pressure swi...

Страница 7: ...ield wiring Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual according to the wiring...

Страница 8: ...phanumeric display may decrease at low temperatures OPERATION The EWWD120 540 units are equipped with a digital controller offering a user friendly way to set up use and maintain the unit This part of...

Страница 9: ...tialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller does not...

Страница 10: ...frigerant in circuit 1 respectively circuit 2 The first number stands for the pressure in bar the second number stands for the saturation temperature in degrees Celsius low pressure of the refrigerant...

Страница 11: ...rcuits The red LED inside the p key lights up and the buzzer inside the controller is activated When a circuit safety occurs the compressor of the corresponding circuit is shut down The screen of the...

Страница 12: ...n the first screen of the network menu To consult information about the outlet water temperature of the evaporator of circuit 1 and 2 only for EWWD360 540 To consult information about the unit status...

Страница 13: ...information about the network safety which caused the shutdown To consult information about the dual pump wich caused the shutdown To check the time and control mode at the moment of the unit shutdown...

Страница 14: ...evaporator and or condenser entering water temperature to control the capacity of the unit outlet control mode uses the evaporator leaving water temperature to control the capacity of the unit To chec...

Страница 15: ...their setting needs to be reset to See User settings menu on page 11 The screen of the user settings menu allows the user to define the schedule timer settings Each day of the week can be appointed to...

Страница 16: ...rd each time he wants to change the setpoint Defining BMS control allows the user to control the unit from a supervisory system The screen and screen of the service menu have to be used to set BMS par...

Страница 17: ...the latest shutdown To check the safety info and the unit status proceed as follows 1 Enter the Refer to the chapter How to enter a menu on page 8 The controller enters the last screen which contains...

Страница 18: ...e g and h keys 6 Press q to confirm the new password When the new password has been confirmed the controller will ask to enter the new password a second time for safety reasons The cursor is positione...

Страница 19: ...panel or measure the supply voltage Voltage too low Measure the supply voltage Overload of motor Reset If the failure persists call your local dealer RESET Push the blue button on the over current rel...

Страница 20: ...apacity of the unit is too low Call your local dealer Water flow is too high Recalculate the water flow The circuit is limited Check the enable disable capacity limitation remote contact POSSIBLE CAUS...

Страница 21: ...perly and that the earth terminals are tightened Refrigerant circuit Check for leaks inside the unit In case a leak is detected call your local dealer Check the working pressure of the unit Refer to p...

Страница 22: ...to the settings in group 2 all Saturdays and Sundays will work according to the settings in group 3 all holiday days will work according to the settings in the holiday group All group settings of gro...

Страница 23: ...1 1 q h q q g h h h g h g h g h g h h g h g 2 0 1 1 1 1 g g h g g h g h g h g h g h g h g g h g h g h g h h g g 1 f 3 3 1 4 3 3 1 3 3 3 3 3 3 3 3 3 2 3 3 3 3 g h g h g h q h h g q h g h g h g h g h g...

Страница 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22685 1...

Отзывы: