Daikin EWWD120MBYNN Скачать руководство пользователя страница 9

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22684-1A

Installation manual

6

Connection and setup of a DICN system 

(See Annex I, 

"Installation examples for a DICN configuration" on

page 9

)

For a system with chillers in a DICN configuration, the chillers have to
be connected as shown in the figure below. 

Make the connection as shown on the wiring diagram using an
AWG20/22 shielded cable, made up of a twisted pair plus shield.

Pay attention to the polarity! TX+ on one chiller must be connected to
TX+ on another chiller. The same for TX– and GND.

Setting the adresses on the digital controller

Set the addresses on the PCB by means of DIP-switches according
to the drawing below:

Where to find the DIP-switches of the digital controller

Important

Be sure to attach — in case of common leaving water control — the
optional temperature sensor.

Cable for remote digital controller

See remote digital controller in the operation manual.

1

A remote digital controller can be connected to the PCB inside
the unit by means of a 6-ray cable and a connector located on
the rear side of the remote digital controller in case you prefer to
operate the unit from a distance. You are allowed to use a cable
of up 

to  600 metres (EWWD120~280) or 300 metres

(EWWD360~540).

  Specifications of the cable: 6-ray telephone

cable with a maximum cable resistance of 0.1 

/m.

2

For units in a DICN configuration, the digital controllers of the
units can be installed remotely at a distance of up to 50 metres
by  using a 6-ray telephone cable with a maximum cable resis-
tance of 0.1 

/m.

Setting the adresses on the remote digital controller

When a remote digital controller is used, the adress has to be set by
means of DIP-switches according to the drawing below:

Where to find the DIP-switches of the remote digital controller

Setting the adresses on the EEV drivers

When EEV drivers are used, the adresses has to be set by means of
DIP-switches according to the drawing below:

Where to find the DIP-switches of the EEV drivers

Master

Slave 1

Slave 2

Slave 3

PCB address

Any unit can be master, slave 1, slave 2, slave 3...

Master

Slave 1

Slave 2

Slave 3

Remote digital 
controller address

Any unit can be master, slave 1, slave 2, slave 3...

1

2

3

4

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

To  avoid damage to the controllers liquid crystals during
winter time, do not shut off the main power supply.

Master

Slave 1

Slave 2

Slave 3

EEV 1 driver

EEV 2 driver

Any unit can be master, slave 1, slave 2, slave 3...

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

Содержание EWWD120MBYNN

Страница 1: ...INSTALLATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Страница 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Страница 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retag...

Страница 4: ...10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication Voltage free contacts general operation pumpcontact alarm operation circuit 1 operation circ...

Страница 5: ...enerated by the unit does not disturb anyone 5 Ensure that water cannot cause any damage to the location in case it drips out of the unit INSPECTING AND HANDLING THE UNIT At delivery the unit should b...

Страница 6: ...d couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWWD120 The water outlet pipe containing the outlet water temperature sen...

Страница 7: ...isted in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes o...

Страница 8: ...ltage free contacts to indicate the status of the unit These voltage free contacts can be wired as described on the wiring diagram The maximum allowable current is 4 A Remote inputs Besides the voltag...

Страница 9: ...s EWWD360 540 Specifications of the cable 6 ray telephone cable with a maximum cable resistance of 0 1 m 2 For units in a DICN configuration the digital controllers of the units can be installed remot...

Страница 10: ...ist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEF...

Страница 11: ...certain measured temperatures inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe off...

Страница 12: ...all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master...

Страница 13: ...shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this bu...

Страница 14: ...Installation manual 11 EWWD120 540MBYNN Packaged water cooled water chillers 4PW22684 1A NOTES...

Страница 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22684 1A...

Отзывы: