Fig. 1 - Lifting the unit
WARNING
Both the lifting ropes and the spacing bar and/or scales must be strong enough to support the machine safely.
Please check the unit’s weight on the machine’s nameplate.
The weights shown in the "Technical data" tables in the "General Information" chapter refer to standard units.
Some specific machines might have accessories that increase their overall weight (heat recovery, etc.)
WARNING
The machine must be lifted with the utmost attention and care. Avoid jolting when lifting and lift the machine very
slowly, keeping it perfectly level.
Positioning and assembly
All units are designed for installation indoors. The machine must be installed on a robust and perfectly level foundation;
should the machine be installed on balconies or roofs, it might be necessary to use weight distribution beams.
For installation on the ground, prepare a strong cement base that is at least 250 mm wider and longer than the machine.
Also, this base must be strong enough to support the weight of the machine as stated in the technical specifications.
If the machine is installed in places that are easily accessible to people and animals, it is advisable to install protection
gratings for the compressor section.
To ensure the best possible performance on the installation site, the following precautions and instructions must be
followed: