Daikin EWAQ080DAYN Скачать руководство пользователя страница 20

Operation manual

19

EWAQ080~260DAYN

Packaged air-cooled water chillers

4PW35556-1E

Tasks of the login/logout menu

Changing the user password

Access to the usersettings menu and the setpoints menu is protected
by the user password (a 4-digit number between 

0000

 and 

9999

).

After the password is entered, other protected screens do no longer
require the entering of the password.

To log out, go to the login/logout menu and alter the login status and
the logout setting.

To change the user password, proceed as follows:

1

Enter the 

USERPASSWORD MENU.

 (Refer to the chapter 

"How

to enter a menu" on page 8

).

The controller will request the password.

2

Enter the actual correct password using the 

Ì

 and 

 keys.

For each of the 4 digits:
-

Use the 

 and 

Ì

 keys to select the correct number.

-

Press the 

 key to enter and select the next number.

When pressing the 

  key on the last number, the complete

password is entered.

3

After the 

 key has been pressed to confirm the password, the

controller shows the first login/logout screen.

The login status is shown.
The logout is set to 

NO

.

4

When the setting for logout must change to 

YES

.

-

Press the 

 key to position the cursor behind 

LOGOUT?

-

Press the 

 or 

Ì

 keys to change the setting to 

YES

.

-

Press the 

 key to confirm the setting.

The controller leaves the login/logout screen and shows the first
screen of the read out menu.

5

When the setting for logout stays 

NO

, press the 

Ì

 key to enter

the second login/logout screen.

The controller requests for a new password.

6

Press the 

 key to position the cursor behind 

NEW PASSWORD

.

7

Enter the new password using the 

Ì

 and 

 keys.

For each of the 4 digits:
-

Use the 

 and 

Ì

 keys to select the correct number.

-

Press the 

 key to enter and select the next number. 

When pressing the 

 key on the last number, the complete 

new password is entered and the cursor is positioned behind 

CONFIRM

.

The controller requests to confirm the new password.

8

Enter the new password again using the 

Ì

 and 

 keys.

For each of the 4 digits:
-

Use the 

 and 

Ì

 keys to select the correct number.

-

Press the 

 key to enter and select the next number. 

When pressing the 

 key on the last number, the 

confirmation of the new password is completed.

T

ROUBLESHOOTING

This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.

Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.

Before contacting your local dealer, read this chapter carefully, it will
save you time and money.

Overview of safety messages

NOTE

The default user password is 

1234

.

NOTE

The actual password will only be changed when the
new password and the confirmed password have the
same value.

If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.

When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.

Message safety menu

Symptom

UNIT SAFETY

0AE:FLOW HAS STOPPED

5.2

0AE:PUMPINTERLOCK

5.3

0A4:FREEZE UP

5.1

0A4:FREEZE UP C1

5.1

0A4:FREEZE UP C2

5.1

0A9:EEV PCB COMM ERR

5.5

0A9:EEV PCB ERR

5.5

0C9:INL SENSOR ERR

7

0CA:OUT SENSOR ERR

7

0H9:AMB T SENSOR ERR

7

0U4:EXTPCB COMM.ERR

9

0U4:MAINPCB COMM.ERR

10

0U5:PCB COMM.PROBLEM

11

CIRCUIT 1 

SAFETY

153:FAN OVERC. ST1

5.4

153:FAN OVERC. ST2

5.4

153:FAN OVERC. ST3

5.4

1A9:EEV ERR

5.5

1A9:SUPERHEAT ERR

5.6

1E3:HIGH PRESSURE SW

5.7

1E4:LOW PRESSURE

5.8

1E6:COMPR 1 SAFETY

5.9b/5.10

1E6:COMPR 2 SAFETY

5.9b/5.10

1F3:HIGH DISCH TEMP1

5.11

1F3:HIGH DISCH TEMP2

5.11

1J3:DISCHSENSOR ERR1

7

1J3:DISCHSENSOR ERR2

7

1J5:REFR SENSOR ERR

7

1J5:SUCTSENSOR ERR

7

1JA:HP SENSOR ERR

7

1JC:LP SENSOR ERR

7

1U1:REV PHASE PROT

5.12

CIRCUIT 2 

SAFETY

253:FAN OVERC. ST1

5.4

253:FAN OVERC. ST2

5.4

253:FAN OVERC. ST3

5.4

2A9:EEV ERR

5.5

2A9:SUPERHEAT ERR

5.6

2E3:HIGH PRESSURE SW

5.7

2E4:LOW PRESSURE

5.8

2E6:COMPR 1 SAFETY

5.9b/5.10

2E6:COMPR 2 SAFETY

5.9b/5.10

2F3:HIGH DISCH TEMP1

5.11

2F3:HIGH DISCH TEMP2

5.11

2J3:DISCHSENSOR ERR1

7

2J3:DISCHSENSOR ERR2

7

2J5:REFR SENSOR ERR

7

2J5:SUCTSENSOR ERR

7

2JA:HP SENSOR ERR

7

2JC:LP SENSOR ERR

7

2U1:REV PHASE PROT

5.12

Содержание EWAQ080DAYN

Страница 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Страница 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Страница 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Страница 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Страница 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Страница 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Страница 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Страница 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Страница 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Страница 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Страница 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Страница 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Страница 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Страница 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Страница 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Страница 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Страница 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Страница 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Страница 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Страница 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Страница 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Страница 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Страница 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Страница 30: ...4PW35556 1E Copyright Daikin...