EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1E

Operation manual

18

Tasks of the info menu

Consulting additional unit information

1

Enter the 

INFO MENU 

through the main menu. (Refer to the

chapter 

"How to enter a menu" on page 8

).

The controller enters the 

TIME INFO

 screen which contains the

following information: the 

TIME

 and 

DATE

.

2

Press 

Ì

 to consult the first 

UNIT INFO 

screen.

This screen contains information about the unit name, number of
circuits, evaporators and coils, EEV and the refrigerant used.

3

Press 

Ì

 to consult the second 

UNIT INFO 

screen.

This screen contains information about the fans, volt/ampere
and if there is a second pump or heater tape applied.

4

Press 

Ì

 to consult the 

SW INFO

 (software information) screen.

This screen contains information about the PCB software
versions.

Tasks of the input/output menu

Checking the status of the inputs and outputs

The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.

The locked digital inputs are:

EMERGENCY STOP

:  whether the emergency button has been

pressed (only effective if there is an emergency stop present).

FLOWSWITCH

:  indicates the status of the flowswitch (flow/no

flow).

HEATER TAPE

: indicates if the heater tape is activated or not.

PUMPINTERLOCK

: indicates if the status of the pump interlock

is open or closed.

PUMP

: indicates if the pump is on or off.

C1

/

2 REV.PH.PROT.

: (reverse phase protector) indicates the

actual status of this safety of circuit 1/2.

C1

/

2 HIGH PR.SW.

:  (high pressure switch) indicates the

actual status of this safety of circuit 1/2.

INT.L C11

/

C12

/

C21

/

22

:  (interlock to compressor) indicates

the actual status of this safety of circuit1/2.

C1

/

2 FANOVERC.

 

ST.

 

1

/

2

/

3

:  (fan overcurrent status

step 1/2/3) indicates the actual status of this safety of circuit 1/2.

The locked relay outputs are:

C11

/

12

/

21

/

22

: indicates whether the circuit 1/2 is on or off.

C1

/

2 FANSTEP 1

/

2

/

3

: indicates if the fans of fanstep 1/2/3 for

the circuit 1/2 are on or not.

Checking the status of the digital changeable inputs and 
outputs

The possible settings for the changeable digital inputs are:

NONE

: indicates there is no function selected for this input

STATUS

: indicates the position of the connected switch.

DUAL SETPOINT

:  indicates the position of the remote dual

setpoint switch: setpoint 1 or setpoint 2.

REMOTE ON/OFF

:  indicates the position of the remote on/off

switch.

CAP LIMIT 25%

/

50%

/

75%

/

SET

:  indicates the position of the

"enable/disable capacity limitation" switches.

LOW NOISE

: indicates the status of the low noise mode.

FREE COOLING REQ

: indicates if the free cooling is requested

or not requested.

FAN FORCED ON

: indicates if the fan forced on is activated or

not activated.

The possible settings for the changeable relay outputs are:

NONE (OPEN)

: Digital output open.

CLOSED

: Digital output closed.

2ND PUMP

: indicates the status of the second pump.

100% CAPACITY

: indicates when the unit is working at 100%.

FULL CAPACITY

:  indicates when the unit is working at

maximum capacity, example reached 100% capacity or reached
maximum capacity because of safety limitation.

FREE COOLING

: indicates the status of the 3-way water valve

when the unit is in free cooling state.

GEN.OPERATION

: indicates when the unit is active.

W (NO)

:  indicates when safety or warning is active

(Normal Open contact).

W (NC)

:  indicates when safety or warning is active

(Normal Closed contact).

SAFETY (NO)

:  indicates when safety is active (Normal Open

contact).

SAFETY (NC)

: indicates when safety is active (Normal Closed

contact).

C1

/

2 SAFETY

: indicates when circuit 1/2 safety is active.

WARNING

: indicates when warning is active.

C1

/

2 OPERATION

:  indicates when circuit 1/2 operation is

active.

Checking the status of the analogue changeable inputs and 
output

The possible settings for the analogue changeable inputs and output
are:

NONE

:  no function is appointed to the changeable analogue

input.

STATUS

: only displays the status by means of test

FLOATING SETP

:  floating setpoint based on ambient or

analogue input

TEMPERATURE

:  only displays the (by example) condenser

outlet temperature

DI***

:  refer to the possible functions for changeable digital

inputs. (*** can be any of the following: 

STATUS

DUAL

SETPOINT

REMOTE ON/OFF,

 

CAP. LIMIT

LOW NOISE

,

FREE COOLING REQ

 or 

FAN FORCED ON

.)

Checking the communication inputs and outputs (option 
EKACPG)

The communication inputs and outputs are:

RS232 ONLINE

: indicates if the RS232 communication line is

active.

RS485 ONLINE

: indicates if the RS485 communication line is

active.

DIII ONLINE

:  indicates if the DIII communication line is

active.

To check the inputs and outputs, proceed as follows:

1

Enter the 

I/O STATUS MENU

.

 

(Refer to the chapter 

"How to

enter a menu" on page 8

.)

The controller enters the first 

DIGITAL INPUTS

 screen.

2

Consult the other screens of the input/output menu using the 

and 

Ì

 keys.

Содержание EWAQ080DAYN

Страница 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Страница 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Страница 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Страница 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Страница 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Страница 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Страница 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Страница 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Страница 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Страница 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Страница 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Страница 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Страница 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Страница 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Страница 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Страница 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Страница 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Страница 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Страница 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Страница 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Страница 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Страница 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Страница 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Страница 30: ...4PW35556 1E Copyright Daikin...

Отзывы: