Daikin EWAQ080DAYN Скачать руководство пользователя страница 17

EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1E

Operation manual

16

Submenu: Language

Defining the language

This screen allows the user to define the language of the displayed
information of the controller (on the first screen). (Push the 

 button

repeatedly to change the operating language).

Submenu: Time and date

Defining the time and date

The 

TIME AND DATE

  screen of the usersettings menu allows the

user to define the time and date.

TIME

: used to define the present time.

DATE FORMAT

: used to define the format of the date.

DATE

:  select the name of the present day and define the

present date according to the setting of the 

DATE FORMAT

.

DD

 = number of day (01~31),

MM

 = number of month (01~12)

YY

 = the last 2 numbers of the year (2006 = 06).

Submenu: Free cooling

Defining free cooling

The 

FREE COOLING

  screen of the usersettings menu allows the

user to control a 3-way water valve when the unit is in free cooling
state. To make this possible a changeable digital input or output has
to be configured for free cooling in the service menu. (Refer to the
installation manual.)

MODE

: used to define the free cooling mode.

NOT ACTIVE

: free cooling is not active.

CHDI

: changeable digital input will activate the free cooling mode

AMBIENT

: free cooling is based on ambient temperature.

INLET-AMBIENT

:  free cooling is based on the difference

between inlet water temperature and ambient temperature.

SP

: setting of the free cooling setpoint.

DIF

: setting of the free cooling difference.

PUMP

ON

: pump will be on when free cooling mode is active

OFF

: pump will be off when free cooling mode is active

LEAD

: time that the pump will be running before the compressor

will start operating.

Submenu: DICN

Only available in case DICN (option kit EKACPG) is installed (refer to
"Connection and setup of a DICN system" in the installation manual
and the installation manual of the EKACPG kit).

Defining the network settings

The 

SETTINGS

  screen of the network menu allows the user to set

the 

MODE

  of the unit, the 

OFFSET

  time and the condition when the

pump must operate.

MODE

:  Define the mode of the unit as 

NORMAL

STANDBY

  or

DISCONN ON/OFF

.

NORMAL

:  The unit is controlled by the network. Loading and

unloading is decided by the central control of the netwerk. Putting
this unit ON or OFF will also put all other units ON or OFF, unless
their status is 

DISCONNECT ON/OFF

. (see further)

Changing 

CONTROL SETTINGS

 

or 

THERMOSTAT

SETTINGS

  to this unit, will apply to all other units. 

MANUAL

CONTROL

 on such a unit is not possible. Refer to 

"Defining and

activating the control mode" on page 14

.

STANDBY

:  The unit is considered as a 

NORMAL

  unit and its

function is then also similar to a unit defined as 

NORMAL

, but this

unit however, will only come into operation if:
another unit is in alarm
another unit is in 

DISCONNECT ON/OFF 

mode

the setpoint is not reached when all other units have been
running on full capacity for some time
If more than one unit is defined as 

STANDBY

, only 1 of the units

will be really standby. The unit which is really standby will be
decided by the number of running hours.

DISCONNECT ON/OFF

: Putting this unit ON or OFF will not put

other units ON or OFF. 

MANUAL CONTROL

  on such a unit is

possible.
If the unit is put to 

INLET

 or 

OUTLET

 mode, and the unit is ON,

it will be controlled by the DICN network as a 

NORMAL

 unit.

OFFSET

:  The 

OFFSET

  time defines the target difference in

running hours between one unit and another unit with

OFFSET:0000h

.  This value is important for maintenance

purposes. The difference in setting among different units should
be high enough as to avoid servicing of the units all at the same
time. The lower and upper limits are 

0

  and 

9000

  hours

respectively. The default value is 

0

 hours.

PUMP ON IF

:  Set if the pump must operate as long as the

chiller is on (

UNIT ON

), or during compressor on condition only

(

COMPR ON

).

When 

UNIT ON

 is selected, the pump output will remain closed

as long as the chiller is on. When 

COMPR ON

  is selected, the

pump output will remain closed as long as the compressor is on.
Also refer to the separate manual "Installation examples for a
DICN configuration".

Submenu: Advanced

Activating or deactivating the setpoints password and the unit 
on/off password

The first 

ADVANCED

 screen of the usersettings menu allows the user

to activate or deactivate the user password needed to change the
temperature setpoint (

SETPOINT MENU

). When deactivated, the

user does not have to enter the password each time he wants to
change the setpoint.

The first 

ADVANCED

 screen of the usersettings menu also allows the

user to activate or deactivate the user password needed to switch the
unit ON or OFF (

UNIT ON/OFF

).

NOTE

A functional diagram showing the free cooling working
can be found in 

"Annex III" on page 26

.

NOTE

Put a unit to 

DISCONNECT ON/OFF 

when servicing

the machine. In this case it is possible to switch ON or
OFF this unit without switching ON or OFF the other
units of the network.

It is also possible then to operate the unit in 

MANUAL

CONTROL

.

Put a unit to 

DISCONNECT ON/OFF 

continuously if

the operator wants to decide by himself when this unit
must operate.

Note that in this case, it makes no sense to define
another unit of the network as 

STANDBY

. Since there is

a unit set continuously to 

DISCONNECT ON/OFF

, the

STANDBY

  unit will continuously be considered as a

NORMAL

 unit.

NOTE

The settings on this screen of the network menu must
be executed for all chillers connected to the system.

NOTE

If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.

Содержание EWAQ080DAYN

Страница 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Страница 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Страница 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Страница 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Страница 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Страница 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Страница 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Страница 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Страница 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Страница 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Страница 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Страница 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Страница 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Страница 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Страница 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Страница 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Страница 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Страница 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Страница 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Страница 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Страница 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Страница 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Страница 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Страница 30: ...4PW35556 1E Copyright Daikin...

Отзывы: