EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1E

Operation manual

12

PUMP

FLOATING SETPOINT

LANGUAGE

TIME AND DATE

FREE COOLING

DICN

ADVANCED

DEFROST

This submenu is not available for EWAQ units.

SERVICE MENU

Timers menu 

Ó

Safety menu 

π

The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.

Along with the basic information, more detailed information screens
can be consulted while the history menu is active. Press the 

 key.

Screens similar to the following will appear. Additionally the number
of safeties that already occurred, can be consulted on the first line of
the history screens.

To define the pump control settings.

To define the dual pump settings.

To define the floating setpoint.

To 

define the controller display

language.

To set the time and date of the system.

To define the free cooling.

The controller displays the name of the
unit: 

MASTER

SLAVE1

  ... 

SLAVE3

.

This name is automatically assigned
depending on the set hardware
address. Refer to "Setting the
addresses" in 

"Connection and setup of

a DICN system"

  in the installation

manual.

To define whether or not a password is
needed to enter the setpoints menu and
for switching the unit on and off.

To define the outlook of the main menu,
to set the logout timer and to define
whether or not the buzzer is to be
activated when errors occur.

To  define the backlight time and to
define whether or not graphic readout is
activated.

To  enter the service menu (only a
qualified installer is allowed to access
this menu).

_v       PUMPCONTROL

PUMPLEADTIME   :020s

PUMPLAGTIME    :060s

DAILY ON:N  AT:12h00

_^        DUAL PUMP

MODE:AUTO ROTATION

OFFSET ON RH   :048h

_  FLOATING SETPOINT

MODE:AMBIENT

MAXPOS:03$0¢ NEG:00$0¢

RF:020$0¢ SLOPE:006$0¢

_           LANGUAGE

PRESS ENTER TO

CHANGE LANGUAGE:

ENGLISH

_      TIME AND DATE

TIME: 22h35

DATE FORMAT:DD/MM/YY

DATE: MON   20/03/06

_       FREE COOLING

MODE:AMBIENT

SP: 05$0¢  DIF:01$0¢

PUMP:ON  LEAD:000s

_÷   MASTER SETTINGS

MODE:NORMAL

OFFSET:0000h

PUMP ON IF:UNIT ON

_v          ADVANCED

PASSWORD NEEDED FOR:

     SETPOINT MENU:Y

       UNIT ON/OFF:Y

_^          ADVANCED

MAIN MENU:GRAPHIC

LOGOUT TIMER  :05min

BUZZER IF SAFETY:YES

_^          ADVANCED

BACKLIGHT TIME:05min

GRAPHIC READOUT:YES

 ENTER SERVICE

   PASSWORD: 0000

   TO LOGIN

To check the actual value of the general
software timer.

To  check the actual value of the
compressor timers of circuit 1. 

To  check the actual value of the
compressor timers of circuit 2 (only for
EWAQ130~260).

To  consult information about the unit
safety which caused the shutdown.

To  consult information about the
circuit 

1 safety which caused the

shutdown.

To  consult information about the
circuit 

2 safety which caused the

shutdown (only for EWAQ130~260).

To  consult information about the
network safety which caused the
shutdown.

To  consult information about the unit
warning which caused the shutdown.

To check the time at the moment of the
unit shutdown and to check which was
the evaporator inlet water temperature
setpoint.

To  check which were the evaporator
inlet, outlet water and ambient tem-
perature at the moment of shutdown.

To  check which was the discharge
temperature of the circuits of circuit 1 at
the moment of shutdown.

To  check which was the discharge
temperature of the circuits of circuit 2 at
the moment of shutdown (only for
EWAQ130~260).

To check which was the temperature of
the refrigerant of circuit 1 at the moment
of shutdown.

To check which was the temperature of
the refrigerant of circuit 2 at the moment
of shutdown (only for EWAQ130~260).

To  check which were the pressures of
circuit 1 and the status of the fans at the
moment of shutdown.

_v    GENERAL TIMERS

LOADUP:000s-DWN:000s

PUMPLEAD   :000s

FLOWSTOP   :00s

_÷ COMPRESSOR TIMERS

 GRD11:000s 12:000s

AREC11:000s 12:000s

M.RT11:000s 12:000s

_^ COMPRESSOR TIMERS

 GRD21:000s 22:000s

AREC21:000s 22:000s

M.RT21:000s 22:000s

_v       UNIT SAFETY

0F0:EMERGENCY STOP

_v   CIRCUIT1 SAFETY

1U1:REV PHASE PROT

_v   CIRCUIT2 SAFETY

1U1:REV PHASE PROT

_v    NETWORK SAFETY

0U4:PCB COMM.PROBLEM

_v  UNIT WARNING

0AE:FLOW HAS STOPPED

_÷  UNIT HISTORY:002

0CA:OUT SENSOR ERR

22h33m00s   23/03/06

  COOL INLSP1:012$0¢

_÷  UNIT HISTORY:002

   INLET WATER:012$0¢

  OUTLET WATER:007$0¢

       AMBIENT:006$5¢

_÷  UNIT HISTORY:002

 C11 DISCHARGE:010$1¢

 C12 DISCHARGE:010$5¢

_÷  UNIT HISTORY:002

 C21 DISCHARGE:010$1¢

 C22 DISCHARGE:010$5¢

_÷  UNIT HISTORY:002

      C1  REFR:000$0¢

_÷  UNIT HISTORY:002

      C2  REFR:000$0¢

_÷  UNIT HISTORY:002

HP1:019$0b = 050$0¢

LP1:019$0b = -05$2¢

LOWNOISE:N  FAN1:OFF

Содержание EWAQ080DAYN

Страница 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Страница 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Страница 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Страница 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Страница 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Страница 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Страница 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Страница 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Страница 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Страница 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Страница 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Страница 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Страница 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Страница 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Страница 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Страница 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Страница 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Страница 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Страница 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Страница 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Страница 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Страница 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Страница 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Страница 30: ...4PW35556 1E Copyright Daikin...

Отзывы: