EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1E

Operation manual

10

CAN STARTUP

:  the circuit is ready to start up when extra

cooling load is needed.

When none of the above mentioned messages appears, no
special functions are active and the compressor is running.

The preceding messages are written down in order of priority.
The 

UNIT CAPACITY

 is written down on the bottom of the first

screen.

7

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

EXTRA READOUT

  screens of the readout menu are

providing the following information:

CURRENT

:  actual current, measured in Ampere (

A

) (only when

OP57 is installed)

VOLTAGE

: actual voltage (

V

) (only when OP57 is installed)

RH11

/

12

/

21

/

22

: actual running hours (

h

)

CS11

/

12

/

21

/

22

: number of compressor start-ups

RHP1

/

2

: actual running hours (

h

) of the pump 1 or 2

8

Press the 

 key to return to the other readout menus.

Adjusting the temperature setpoint

The unit provides definition and selection of four independent
temperature setpoints. Two setpoints are reserved for inlet control,
the other two are reserved for outlet control.

COOL. INLSP1

: inlet water temperature, setpoint 1,

COOL. INLSP2

: inlet water temperature, setpoint 2.

COOL. OUTSP1

: outlet water temperature, setpoint 1,

COOL. OUTSP2

: outlet water temperature, setpoint 2.

The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.

If the manual control mode is selected (refer to 

"Usersettings menu

Å

" on page 11

), none of the above-mentioned setpoints will be

active.

To adjust a setpoint, proceed as follows:

1

Enter the setpoints menu. Refer to the chapter 

"How to enter a

menu" on page 8

.

If the user password is disabled for setpoint modifications (refer
to 

"Usersettings menu 

Å

" on page 11

), the controller will

immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the 

  and 

Ì

  keys (refer to 

"User

password menu 

Æ

" on page 14

). Press 

  to confirm the

password and to enter the setpoints menu.

2

Select the setpoint to be adjusted using the 

 key.

A setpoint is selected when the cursor is blinking behind the
setpoint's name.
The "

>

" sign indicates the actual active temperature setpoint.

3

Press the 

 and 

Ì

 keys to adjust the temperature setting.

The default, limit and step values for the cooling temperature
setpoints are:

4

Press 

 to save the adjusted temperature setpoint.

When the setting has been confirmed, the cursor switches to the
next setpoint.

5

To adjust other setpoints, repeat from step 2.

Resetting the unit

The units are equipped with three kinds of safety devices: unit
safeties, circuit safeties and network safeties.

When a unit or circuit safety occurs, the compressor is shut down.
The safeties menu will indicate which safety is activated. The 

UNIT

STATUS

 screen of the readout menu will indicate 

OFF - SAFETY

ACTIVE

.  The red LED inside the 

π

  key  lights up and the buzzer

inside the controller is activated.

When a network safety occurs in a DICN configuration, the slaves not
detected by the network will function as stand alone units.

If a slave unit can not be found by the network, the red light
inside the 

π

 key of the master lights up and the buzzer inside

the control is activated.

If the master can not be found by the network, the red light
inside the 

π

 key of all the slaves light up and the buzzer inside

their controls are activated. All units will work as stand alone
units.

If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.

To reset the unit, proceed as follows:

1

Press the 

π

 key to acknowledge the alarm.

The buzzer is deactivated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or circuit safety or
network safety.

2

Find the cause of shutdown and correct.

Refer to 

"Listing activated safeties and checking the unit status"

on page 17

 and 

"Troubleshooting" on page 19

.

When a safety can be reset, the LED under the 

π

  key  starts

blinking.

3

Press the 

π

 key to reset the safeties that are no longer active.

If required, enter the 

USER PASSWORD

  or the 

SERVICE

PASSWORD

.  (Refer to the installation manual "Setting the

password for safety reset".)
Once all safety devices are deactivated and reset, the LED
under the 

π

 key goes out. If one of the safeties is still active, the

LED under the 

π

  key  goes on again. In this case, return to

step 2.

4

It will only be necessary to switch the 

œ

 key on again if a unit

safety occurs.

NOTE

The customer is also allowed to define a setpoint in
function of an analogue input.

NOTE

Refer to "Customization in the service menu" chapter
"Setting of the changeable inputs and outputs" in the
installation manual

COOLING INLET SETP

COOLING OUTLET SETP

default value

12¢

limit values

(*)

(*)

For glycol treated units with OPZH installed, the lower limit of the cooling 
temperature setpoint can be adapted by changing the minimum operating 
temperature in the service menu (refer to the installation manual).

 23¢

 20¢

step value

0$1¢

0$1¢

NOTE

When a setpoint on a unit in a DICN system is set, this
setpoint will be transferred to all other units.

NOTE

Also consult 

"Defining the floating setpoint settings" on

page 15

.

If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.

NOTE

The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.

Содержание EWAQ080DAYN

Страница 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Страница 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Страница 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Страница 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Страница 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Страница 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Страница 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Страница 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Страница 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Страница 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Страница 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Страница 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Страница 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Страница 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Страница 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Страница 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Страница 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Страница 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Страница 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Страница 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Страница 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Страница 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Страница 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Страница 30: ...4PW35556 1E Copyright Daikin...

Отзывы: