EWAQ080~260DAYN

Packaged air-cooled water chillers

4PW35556-1E

Switching the unit off

If no remote on/off switch is configured:

Press the 

œ

 key on the controller.

The LED inside the 

œ

 key goes out.

If a remote on/off switch is configured:

Press the 

œ

 key on the controller or switch the unit off using the

remote on/off switch.
The LED inside the 

œ

 key goes out in the first case and starts

blinking in the second case.

Switching units ON/OFF in a DICN system

If the 

œ

 key is pressed on a unit with status 

NORMAL

 or 

STANDBY

, all

other units with status 

NORMAL

 or 

STANDBY

 will be ON or OFF.

If the 

œ

 key is pressed on a unit with status 

DISCONNECT ON/OFF

,

only this unit will be ON or OFF.

Consulting actual operational information

1

Enter the readout menu. Refer to the chapter 

"How to enter a

menu" on page 8

.

The controller automatically shows the first screen of the
readout menu which provides the following information:

cooling mode

§

heating mode

fan (

H

 high or 

L

 low)

¡

low noise mode activated (only available when option
OPIF is installed)

pump on

…1

/

2

in case of dual pump control: pump 1/2 on

∞11

/

12

circuit 1 compressor 1/2 on

∞21

/

22

circuit 2 compressor 1/2 on

alarm and last occured malfunction code (

0U4

  in

example)

13$6¢

actual temperature (inlet or outlet temperature
depending on active mode)

12$0¢

temperature setpoint (inlet or outlet temperature
depending on active mode)

2

Press the 

Ì

 key to enter the next screen of the readout menu.

MANUAL MODE

 or 

COOL INLSP1

/

2

 or 

COOL OUTLSP1

/

2

:

manual/automatic control mode operation. If the automatic
control mode is selected, the controller will indicate the active
temperature setpoint. Depending on the status of the remote
contact, setpoint one or setpoint two is active.

INL WATER

: actual inlet water temperature.

OUTL WATER

: actual outlet water temperature.

AMBIENT

: actual ambient temperature.

3

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

TEMPERATURE

  screen of the readout menu provides

information concerning the discharge temperature of the
compressors (

C11

 and 

C12

/

C21

 and 

C22

).

4

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

C1

/

C2 TEMP. READOUT

  screen of the readout menu

provides information concerning the refrigerant temperature
(

REFR

) of circuit 1/circuit 2.

5

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

ACT. PRESSURES

  screen of the readout menu provides

information concerning the actual pressures of circuit.

HP1/2

: high pressure of the refrigerant in circuit 1/2. The first

number stands for the pressure in bar, the second number
stands for the bubble point saturation temperature in degrees
Celsius.

LP1/2

: low pressure of the refrigerant in circuit 1/2. The first

number stands for the pressure in bar, the second number
stands for the dew point saturation temperature in degrees
Celsius.

LOWNOISE

: at the bottom of the first screen, the status of the

lownoise setting is shown (

Y

=active or 

N

=not active).

6

Press the 

Ì

 key to enter the next screen of the readout menu.

The 

UNIT STATUS

  screen of the readout menu provides

information concerning the status of the different circuits.

C11

 and 

C12

: actual status of circuit 1 (

ON

 or 

OFF

).

C21

 and 

C22

: actual status of circuit 2 (

ON

 or 

OFF

).

When the unit is on and a circuit is 

OFF

, the following status

information may appear.

SAFETY ACT.

:  one of the circuit safety devices is activated

(refer to 

"Troubleshooting" on page 19

).

FREEZEUP DIS

: the compressor is disabled by the freeze-up

disable function.

FREEZEUP PR

: freeze-up prevention is active.

HP SETBACK

: high pressure setback is active.

MIN.RUN.TIM

:  minimum running time of the compressor is

active.

LIMIT

: the compressor is limited by the limitation function.

STANDBY DICN

:  when in a DICN configuration, the unit is in

stand by mode because there is sufficient current capacity to
maintain set point.

UNIT OFF

: the unit is switched off.

AREC INLET

:  the compressor will not start up when the inlet

water temperature has not risen enough compared to previous
switch off of the compressor.

FREE COOLING

: free cooling mode is active

TIMER BUSY

: the actual value of one of the compressor timers

is not zero (refer to 

"Timers menu 

Ó

" on page 12

).

PUMPLEAD TIM

: the compressor will wait to start up for as long

as the pump lead timer is counting down.

NO FLOW

: there is no flow after pumplead, the unit is in stand-by

mode.

NO PRIORITY

: This compressor will not start up because it has

no priority. Refer to 

"Defining the lead-lag settings" on page 15

 for

adjusting the priority.

NOTE

Also consult "Customization in the service menu"
chapter "Setting of the changeable inputs and outputs"
in the installation manual.

NOTE

When a remote ON/OFF switch is configured, the
remote ON/OFF contact for all units with status

NORMAL

 or 

STANDBY

 of a DICN network is the contact

connected to the master unit.

For units with status 

DISCONNECT ON/OFF

, the

remote contact is the contact connected to this unit.

NOTE

If the user wants 1 unit to operate on his command
only, this unit is to be set to 

DISCONNECT ON/OFF

.

It is recommended not to select the master unit for this
purpose. Even if the status of the master is set to

DISCONNECT ON/OFF

, it will still be the contact

connected to the master which will switch ON/OFF the
other units in 

NORMAL

  or 

STANDBY

  mode. It would

therefore never be possible to only switch the master
unit OFF remotely.

Switching OFF the master unit only, should in this case
be done by the local ON/OFF key on the master unit.

_v¶¡

…   ≤0U4 

013$6¢

∞11 ∞12 ≠H    012$0¢

∞21 ∞22 ≠H

NOTE

For a DICN system, the 

INLET WATER

 and 

OUTLET

WATER

  values are the values of the individual units,

not of the system. Temperatures of the system can be
consulted in the first screen of the network menu.

Содержание EWAQ080DAYN

Страница 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Страница 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Страница 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Страница 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Страница 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Страница 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Страница 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Страница 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Страница 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Страница 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Страница 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Страница 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Страница 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Страница 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Страница 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Страница 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Страница 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Страница 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Страница 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Страница 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Страница 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Страница 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Страница 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Страница 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Страница 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Страница 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Страница 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Страница 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Страница 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Страница 30: ...4PW35556 1E Copyright Daikin...

Отзывы: