6.1.3 Unit Rapid Stop Alarms
The unit is immediately stopped. All the running circuits will stop rapidly without performing the
normal shutdown procedure.
6.1.3.1 EXV drive circuit #1/#2 communication fail alarm (W/C only)
This alarm is generated in case of communication problems with the EXV driver of circuit #1 or
circuit #2 identified respectively with labels EEXV-1 and EEXV-2.
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Unit Off Exv*CtrlCommFail
String in the alarm log:
Unit Off Exv*CtrlCommFail
String in the alarm snapshot:
Unit Off Exv*CtrlCommFail
Module has no power supply
Check the power supply from the
connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is
tightly inserted in the module
Module address is not properly set
Check if module’s address is correct
referring to the wiring diagram.
Module is broken
Check if LED are on and both green.
If BSP LED is solid red replace the
module
Check if power supply is ok but LEDs
are both off. In this case replace the
module
* refers to either driver #1 or driver #2
6.1.3.2 Options controller communication fail alarm
This alarm is generated in case of communication problems with the module for optional functions.
POL965 with address 18. This alarm can occurs only if the at least one of the optional functions is
enabled (PVM, External Alarm, Demand Limit, LWT Reset; see section 0)
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Unit Off OptCtrlrComFail
String in the alarm log:
Unit Off OptCtrlrComFail
String in the alarm snapshot:
Unit Off OptCtrlrComFail
Module has no power supply
Check the power supply from the
connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is
tightly inserted in the module
Module address is not properly set
Check if module’s address is correct
referring to the wiring diagram.
Module is broken
Check if LED are on and both green.
If BSP LED is solid red replace the
module
Check if power supply is ok but LEDs
are both off. In this case replace the
module
6.1.3.3 Phase Voltage Monitor alarm
Resolution of this fault requires a direct intervention on the power supply of this unit.
Direct intervention on the power supply can cause electrocution, burns or even death. This action
must be performed only by trained persons. In case of doubts contact your maintenance company.
This alarm is generated in case of problems with the power supply to the chiller. This alarm can
occur only if the PVM is enabled (see section 4.9.1)