Installation manual
21
EWAQ+EWYQ009~0 EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
User permission level
00
User permission level
3
2/3
1
—
1
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_TI)
40
25~55
1
°C
03
Set point at high ambient temperature (Hi_TI)
25
25~55
1
°C
2
Not available
3
Auto restart
00
Status
0 (ON)
0/1
—
—
4
Not available
5
Not available
6
Not available
7
Not available
8
Not available
9
Cooling and heating set point ranges
00
Heating set point upper limit
55
37~55
1
°C
01
Heating set point lower limit
15
15~37
1
°C
02
Cooling set point upper limit
22
18~22
1
°C
03
Cooling set point lower limit
5
5~18
1
°C
04
Overshoot setting
2
1~4
1
°C
A
Quiet mode
00
Quiet mode type
0
0/2
—
—
01
Parameter 01
3
—
—
—
C
Alarm output logic of EKRP1HB
00
Not applicable. Do not change the default value!
0
—
—
—
01
Output logic of the EKRP1HB remote alarm
input/output PCB
0
0/1
—
—
D
Benefit kWh rate power supply
00
Not available
01
Unit connection to benefit kWh rate power supply
0 (OFF)
0/1/2
—
—
02
Not applicable. Do not change the default value!
0
—
—
—
E
Unit information readout
00
Software version
Read
only
—
—
—
01
EEPROM version
Read
only
—
—
—
02
Unit model identification
Read
only
—
—
—
03
Liquid refrigerant temperature
Read
only
—
—
°C
04
Inlet water temperature
Read
only
—
—
°C