10

Connecting the water circuit

Water connections must be made in accordance with the outlook
diagram delivered with the unit, respecting the water in- and outlet.

If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:

Use clean pipes only.

Hold the pipe end downwards when removing burrs.

Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.

Use a good thread sealant for the sealing of the connections.
The sealing must be able to withstand the pressures and
temperatures of the system.

When using non-brass metallic piping, make sure to insulate
both materials from each other to prevent galvanic corrosion.

Because brass is a soft
material, use appropriate tooling
for connecting the water circuit.
Inappropriate tooling will cause
damage to the pipes.

Protecting the water circuit against freezing

Frost can damage the unit. For this reason, in colder climates the
water circuit can be protected by means of a heater tape option
(OP10) or by adding glycol to the water.

In case of heater tape

Check that the unit has the option heater tape installed (factory
mounted). Units with option heater tape have the possibility to install
an extra heatertape to protect the waterpipe outside the unit against
freezing. (Field supply, maximum 200 W, connections must be made
on terminals 5/6 inside the switchbox).

In case of glycol 

Depending on the expected lowest outdoor temperature, make sure
the water system is filled with a weight concentration of glycol as
mentioned in the table below.

Also refer to 

"Checks before initial start-up" on page 16

.

Charging water

1

Connect the water supply to a drain and fill valve (see 

"Main

components" on page 7

).

2

Make sure the automatic air purge valve is open (at least 2
turns).

3

Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as
possible using the air purge valves. Air present in the water
circuit might cause malfunctioning.

Piping insulation

The complete water circuit, inclusive all piping, must be insulated to
prevent condensation during cooling operation and reduction of the
cooling and heating capacity as well as prevention of freezing of the
outside water piping during winter time. The thickness of the sealing
materials must be at least 13 mm with 

λ

 = 0.036 in order to prevent

freezing on the outside water piping.

If the temperature is higher than 30°C and the humidity is higher than
RH 80%, then the thickness of the sealing materials should be at
least 20 mm in order to avoid condensation on the surface of the
sealing.

Be careful not to deform the unit piping by using excessive
force when connecting the piping. Deformation of the
piping can cause the unit to malfunction.

The unit is only to be used in a closed water system.
Application in an open water circuit can lead to
excessive corrosion of the water piping.

Never use Zn-coated parts in the water circuit.
Excessive corrosion of these parts may occur as
copper piping is used in the unit's internal water
circuit.

For the heater tape to operate, power to the unit must be
provided and the main isolator switch must be on. For this
reason never disconnect power and never turn off the main
isolator switch for a long time during cold periods!

Minimum 

outdoor temperature 

Ethylene glycol

Propylene glycol

–5°C

10%

15%

–10°C

25%

25%

–15°C

35%

35%

Corrosion of the system due to presence of glycol

Uninhibited glycol will turn acidic under the influence of
oxygen. This process is accelerated by presence of copper
and at higher temperatures. The acidic uninhibited glycol
attacks metal surfaces and forms galvanic corrosion cells
that cause severe damage to the system.

It is therefore of extreme importance:

that the water treatment is correctly executed by a
qualified water specialist;

that a glycol with corrosion inhibitors is selected to
counteract acids formed by the oxidation of glycols;

that no automotive glycol is used because their
corrosion inhibitors have a limited lifetime and contain
silicates which can foul or plug the system;

that galvanized piping is not used in glycol systems
since its presence may lead to the precipitation of
certain components in the glycol’s corrosion inhibitor;

that it has to be made sure the glycol is compatible
with the used materials in the system.

NOTE

Be aware of the hygroscopic property of glycol: it
absorbs moisture from its environment.

Leaving the cap off the glycol container causes the
concentration of water to increase. The glycol
concentration is then lower than assumed. And in
consequence, freezing can happen after all.

Preventive actions must be taken to ensure minimal
exposure of the glycol to air.

NOTE

During filling, it might not be possible to remove all
air in the system. Remaining air will be removed
through the automatic air purge valves during first
operating hours of the system. Additional filling
with water afterwards might be required.

The water pressure indicated on the manometer
will vary depending on the water temperature
(higher pressure at higher water temperature).

However, at all times water pressure should
remain above 0.3 bar to avoid air entering the
circuit.

The unit might dispose some excessive water
through the pressure relief valve.

Содержание EWAQ-ACV3

Страница 1: ...anual Packaged air cooled water chillers and packaged reversible air to water heatpumps EWAQ ACV3 009 010 011 EWYQ ACV3 009 010 011 EWAQ ACW1 009 011 013 EWYQ ACW1 009 011 013 Refrigerant R410A Code 4PW51587 1A Date ...

Страница 2: ...W1 V3 2 1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 DC AC DC AC 1 2 ...

Страница 3: ...a dodržení ustanovení předpisu 15 prema odredbama 16 követi a z 17 zgodnie z postanowieniami Dyrektyw 18 în urma prevederilor 19 ob upoštevanju določb 20 vastavalt nõuetele 21 следвайки клаузите на 22 laikantis nuostatų pateikiamų 23 ievērojot prasības kas noteiktas 24 održiavajúc ustanovenia 25 bunun koşullarına uygun olarak 01 Note as set out in A and judged positively by B according to the Cert...

Страница 4: ...is designed for outdoor installation and used for both heating and cooling applications The unit is designed to be combined with fan coil units or air handling units for air conditioning purposes Heat pump and cooling only versions This chiller range consists of 2 main versions a heat pump EWYQ version and a cooling only EWAQ version available in 6 standard sizes V3 9 10 and 11 kW single phase W1 ...

Страница 5: ...the local laws and regulations and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not act on the terminal connections or wires Incomplete connection or fixing may cause a fire ...

Страница 6: ...that in factories In vehicles or vessels Where acidic or alkaline vapour is present BEFORE INSTALLATION Installation Be sure to confirm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the tightening torque does not exceed 4 1 N m In case ambient temperatures below 0 C are expected counte...

Страница 7: ...tall the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction 6 When installing the unit in a place frequently exposed to snow pay special attention to elevate the foundation as high as possible 7 If you install the unit on a building frame please install a waterproof plate field supply withi...

Страница 8: ...for laying the upper unit s drain pipe Get the portion A sealed so that air from the outlet does not bypass C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row 2 In case of installing multiple units 2 units or more in lateral connection per row Relation of dimensions of H A and L are shown in the table below A Location of the 2 fixation holes on the...

Страница 9: ...mer will select cooling or heating on the room thermostat T This selection is not possible by operating the user interface When cooling heating is requested by the room thermostat T the pump will start operating and the unit will switch to cooling mode heating mode The unit will start operating to achieve the target leaving cold hot water temperature The ON OFF setting of the heating cooling opera...

Страница 10: ... The water filter must be cleaned on a regular base See Maintenance on page 22 12 Manometer The manometer allows readout of the water pressure in the water circuit 13 Flow switch The flow switch checks the flow in the water circuit and protects the heat exchanger against freezing and the pump against damage 14 Pump The pump circulates the water in the water circuit 15 Pressure relief valve The pre...

Страница 11: ...ion to a water circuit This circuit must be provided by a licensed technician and must comply with all relevant European and national regulations Before continuing the installation of the unit check the following points The maximum water pressure is 3 bar Drain taps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance A drain valve is provi...

Страница 12: ... l is higher than 280 l the pre pressure must be decreased see table above The required pre pressure is Pg H 10 0 3 bar 0 10 0 3 bar 0 3 bar The corresponding maximum water volume can be read from the graph approximately 410 l Since the total water volume 350 l is below the maximum water volume 410 l the expansion vessel suffices for the installation Setting the pre pressure of the expansion vesse...

Страница 13: ... than 30 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Be careful not to deform the unit piping by using excessive force when connecting the piping Deformation of the piping can cause the unit to malfunction The unit is only to be used in a closed water system Application in ...

Страница 14: ...n switch C1 C4 Capacitor DS1 DIP switch E1HC Crankcase heater F1U F3U F4U Fuse 6 3 A T 250 V F6U Fuse 5 0 A T 250 V H1P H7P Orange LED service monitor A2P H2P prepare test flickering H2P malfunction detection light up HAP A1P Green LED service monitor K1R Magnetic relay Y1S K4R Magnetic relay E1HC K10R K11R Magnetic relay L1R Reactor M1C Motor compressor M1F Motor upper fan M2F Motor lower fan PS ...

Страница 15: ...id valve 4 way valve Y3S Solenoid valve Z1C Z9C Noise filter ferrite core Z1F Z4F Noise filter Door 2 electrical parts of the hydraulic compartment A11P Main PCB A12P User interface PCB A4P Remote alarm PCB EKRP1HB E6H Expansion vessel heater E7H Water piping heater E8H Heatertape field supply max 200 W FU1 Fuse 3 15 A T 250 V for PCB FU2 Fuse 5 A T 250 V FuR FuS Fuse 5 A 250 V for remote alarm PC...

Страница 16: ...ase The wiring diagram can be found on the inside of the front plate of the unit Connection of the thermostat cable Connection of the thermostat cable depends on the application See also Typical application examples on page 6 Thermostat requirements Contact voltage 230 V Procedure 1 Connect the thermostat cable to the appropriate terminals as shown on the wiring diagram 2 Fix the cable with cable ...

Страница 17: ...at the equipment only consumes a limited amount of electricity during certain periods of time The unit is designed to receive an input signal by which the unit switches into forced off mode At that moment the unit compressor will not operate Thermostat Configuration Pump operation o o o o p p p pr r r r No thermostat wiring on when unit is on UI UI UI Thermostat with heating cooling switch wiring ...

Страница 18: ...asten the digital controller on a flat surface 1 Benefit kWh rate power supply box 2 Receiver controlling the signal of the electricity company 3 Power supply to unit 4 Voltage free contact 0 Allowed for all models X Not allowed for OP10 models allowed for other models 1 When the signal is released again the voltage free contact will close and the unit will restart operation It is therefore import...

Страница 19: ...ording to the wiring diagrams and according to European and national regulations 2 Fuses or protection devices Check that the fuses or the locally installed protection devices are of the size and type specified in the chapter Technical specifications on page 25 Make sure that neither a fuse nor a protection device has been bypassed 3 Earth wiring Make sure that the earth wires have been connected ...

Страница 20: ...controller check for voltage imbalance If the error code L4 is displayed on the remote controller it is possible that air inlet or air outlet are blocked The reversed phase protection detector of this product only works during the initialisation stage after a power reset The reversed phase protection detector is designed to stop the product in case of an abnormality when the product is started up ...

Страница 21: ...t field setting 5 Save the new value by pressing the pr button 6 Repeat step 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and...

Страница 22: ...d 9 00 Heating set point upper limit maximum leaving water temperature for heating operation 9 01 Heating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation 9 04 Overshoot setting defines how...

Страница 23: ...y company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identification example 11 E 03 Readout of the liquid refrigerant temperature E 04 Readout of the inlet water temperature D 00 Compressor 0 default Forced off 1 Forced off 2...

Страница 24: ...ailable 6 Not available 7 Not available 8 Not available 9 Cooling and heating set point ranges 00 Heating set point upper limit 55 37 55 1 C 01 Heating set point lower limit 15 15 37 1 C 02 Cooling set point upper limit 22 18 22 1 C 03 Cooling set point lower limit 5 5 18 1 C 04 Overshoot setting 2 1 4 1 C A Quiet mode 00 Quiet mode type 0 0 2 01 Parameter 01 3 C Alarm output logic of EKRP1HB 00 N...

Страница 25: ... 3 Water pressure relief valve Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise If you do not hear a clacking sound contact your local dealer In case the water keeps running out of the unit close both the water inlet and outlet shut off valves first and then contact your local dealer 4 Pressure relief valve hose Check that the pressure...

Страница 26: ... low Check that all shut off valves of the water circuit are completely open Check if the water filter needs cleaning Make sure there is no air in the system purge air Check on the manometer that there is sufficient water pressure The water pressure must be 0 3 bar water is cold 0 3 bar water is hot Check that the pump speed setting is on the highest speed Make sure that the expansion vessel is no...

Страница 27: ...rmistor is giving the correct read out A1 Hydraulic PCB defective Contact your local dealer A5 Too low during cooling operation or too high during heating operation refrigerant temperature measured by R13T Contact your local dealer C0 Flow switch failure flow switch remains closed while pump is stopped Check that the flow switch is not clogged with dirt C4 Heat exchanger thermistor failure heat ex...

Страница 28: ... nipple refrigerant liquid side Ø9 5 mm 3 8 inch Ø9 5 mm 3 8 inch refrigerant gas side Ø15 9 mm 5 8 inch Ø15 9 mm 5 8 inch Expansion vessel volume 10 l 10 l maximum working pressure MWP 3 bar 3 bar Pump type water cooled water cooled no of speed 2 2 Sound pressure level b heating 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 52 dBA cooling 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 52 dBA 51 dBA...

Страница 29: ...NOTES NOTES ...

Страница 30: ...acy reliability or fitness for particular purpose of its content and the products and services presented therein Specifications are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publication All content is copyrighted by Daikin Europe N...

Отзывы: