Daikin EWAP400MBYNN Скачать руководство пользователя страница 9

EWAP400~540MBYNN

Packaged air-cooled water chillers

4PW22678-1B

Installation manual

6

Setting the adresses on the digital controller

Set the addresses on the PCB by means of DIP-switches according
to the drawing below:

Where to find the DIP-switches of the digital controller

Important

Be sure to attach – in case of common leaving water control – the
optional temperature sensor.

Cable for remote digital controller

See remote digital controller in the operation manual.

1

A remote digital controller can be connected to the PCB inside
the unit by means of a 6-ray cable and a connector located on
the rear side of the remote digital controller in case you prefer to
operate the unit from a distance. You are allowed to use a cable
of up to 600 metres. Specifications of the cable: 6-ray telephone
cable with a maximum cable resistance of 0.1 

/m.

2

For units in a DICN configuration, the digital controllers of the
units can be installed remotely at a distance of up to 60 metres
by  using a 6-ray telephone cable with a maximum cable
resistance of 0.1 

/m.

Setting the adresses on the remote digital controller

When a remote digital controller is used, the adress has to be set by
means of DIP-switches according to the drawing below:

Where to find the DIP-switches of the remote digital controller

B

EFORE

 

STARTING

I do confirm having executed and checked all the above
mentioned items.

Keep for future reference.

Master

Slave 1

Slave 2

Slave 3

PCB 
address

Any unit can be master, slave 1, slave 2 or slave 3.

Master

Slave 1

Slave 2

Slave 3

Remote digital 
controller address

Any unit can be master, slave 1, slave 2, slave 3...

To  avoid damage to the controllers liquid crystals during
winter time, do not shut off the main power supply.

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

1 2 3 4 5 6

OFF

The unit should not be started, not even for a very short
period of time, before the following pre-commissioning
checklist is filled out completely.

tick 

 

when 

checked

standard steps to go through before starting the unit

1

Check for external damage.

2

Open all shut-off valves indicated by a red label: "OPEN THIS 
VALVE BEFORE OPERATION". (Open the liquid line, discharge 
and suction (if provided) stop valves completely.)

3

Install main fuses, earth leak detector and main switch.

Recommended fuses: aM according to IEC standard 269-2.

Refer to the wiring diagram for size.

4

Supply the main voltage and check if it is within the allowable 
±10% limits of the nameplate rating.

The electrical main power supply should be arranged so, that 
it can be switched on or off independently of the electrical 
supply to other items of the plant and equipment in general.

Refer to the wiring diagram, terminals L1, L2 and L3.

5

Supply water to the evaporator and verify if water flow is within 
the limits as given in the table under 

"Water charge, flow and 

quality" on page 4

.

6

The piping must be completely purged

7

Connect the pump contact in series with the contact of the 
flowswitch, so that the unit can only come in operation when the 
waterpumps are running and the water flow is sufficient.

For DICN configurations, every chiller shall have its own 
flowswitch and shall be interlocked with the pump from which it 
gets the flow.

8

Check the oil level in the compressors.

9

Connect the power supply to the heatertapes.

The heatertapes must be connected to an independent, 
separately fused, power supply all year-round.

10

Install the filter kit supplied with the unit in front of the 
evaporator water inlet. The filter has a mesh size of maximum 
1.0 mm.

11

Check that all the water sensors are correctly fixed into the 
heat exchanger (see also the sticker attached to the heat 
exchanger).

NOTE

It is necessary to read the operation manual
delivered with the unit before operating the unit. It
will contribute to understand the operation of the
unit and its electronic controller.

Close all switch box doors after installation of the unit.

Date

Sign

Содержание EWAP400MBYNN

Страница 1: ...INSTALLATION MANUAL EWAP400MBYNN EWAP460MBYNN EWAP540MBYNN Packaged air cooled water chillers...

Страница 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Страница 3: ...nderung 03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med...

Страница 4: ...grills BMS Connection MODBUS J BUS BACNET LON Inverter fans Heat recovery High ESP fans Features Stepless capacity control 15 100 Evaporator heater tape Glycol application for leaving evaporator wate...

Страница 5: ...the unit and the floor is flat to prevent vibration and noise generation 2 The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet refer to the operatio...

Страница 6: ...or I beam frame to support the unit on the roof or it can be installed on a concrete base Ground level mounted The unit must be installed on a solid base It is recommended to fix the unit on a concret...

Страница 7: ...To assure proper operation of the unit the water flow through the evaporator must be within the operation range as specified in the table below and a minimum water volume is required in the system Th...

Страница 8: ...note the following Switch for remote on off Units with status or will be controlled by the remote on off switch connected to the chiller defined as Units with status are controlled by the switch conne...

Страница 9: ...not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for...

Страница 10: ...s to comply Defining of the changeable digital analog inputs and outputs Besides locked inputs and outputs there are a number of changeable inputs and outputs of which the function can be chosen from...

Страница 11: ...from a supervisory system If set to no the supervisory system can only read out values but cannot modify them used to address the PCB indicates the communication protocol If the optional gateway is us...

Страница 12: ...ll units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master u...

Страница 13: ...em configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this buffer One unit s...

Страница 14: ...Installation manual 11 EWAP400 540MBYNN Packaged air cooled water chillers 4PW22678 1B NOTES...

Страница 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergenc...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22678 1B...

Отзывы: