Daikin EWAP400MBYNN Скачать руководство пользователя страница 8

Installation manual

5

EWAP400~540MBYNN

Packaged air-cooled water chillers

4PW22678-1B

F

IELD

 

WIRING

Parts table

F11U-F13U ............Main fuses circuit 1 (standard)

F21U-F23U ............Main fuses circuit 2 (standard)

F1,2,3U ..................Main fuses for the unit (OP52)

F4,5U .....................Fuses for the evaporator heatertape

H1P ........................Indication lamp general operation

H2P ........................Indication lamp alarm

H3,4P .....................Indication lamp operation circuit 1, circuit 2

L1,2,3 .....................Main terminals

PE ..........................Main earth terminal

S6S ........................Changeable input 1

S8L.........................Flowswitch

S9L.........................Contact that closes if the pump is working

S10S ......................Changeable input 2

S11S ......................Changeable input 3

S12S ......................Changeable input 4

S13S ......................Main isolator switch

- - -..........................Field wiring

Power circuit and cable requirements

1

The electrical power supply to the unit should be arranged so
that it can be switched on or off independently of the electrical
supply to other items of the plant and equipment in general.

2

A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector. Recommended fuses are mentioned on the wiring
diagram supplied with the unit.

Connection of the air-cooled water chiller power supply

1

Using the appropriate cable, connect the power circuit to the L1,
L2 and L3 terminals of the unit.

In case the option "main isolator switch" is installed on the unit,
the power circuit must be connected to the terminals 2, 4 and 6
of the main isolator switch.

2

Connect the earth conductor (yellow/green) to the earthing
terminal PE.

Interconnection cables

Heater tape power supply
The evaporator and heat recovery condensor heater tape is
supplied with the unit. The heater tape must be connected to an
independent supply 1~50 Hz, 230 V and must be connected
year-round. Separate fuses have to be installed in the field (refer
to the wiring diagram supplied with the unit).

Voltage free contacts
The controller is provided with some voltage free contacts to
indicate the status of the unit. These voltage free contacts can
be wired as described on the wiring diagram. The maximum
allowable current is 4 A.

Remote inputs
Besides the voltage free contacts, there are also possibilities to
install remote inputs.
They can be installed as shown on the wiring diagram.

For units in DICN configuration, note the following:

Switch for remote on/off:
Units with status 

 or 

 

 will be controlled by the

remote on/off switch connected to the chiller defined as

.

Units with status 

   

are controlled by the

switch connected to them.
See also operation manual: "Selecting local or remote on/off
control".

Remote dual setpoint switch:
The remote dual setpoint switch should only be connected to
the chiller defined as 

.

However in case the master drops out because of e.g. a
power supply failure, it might be interesting to have the dual
temperature switch installed to the other units as well.

Connection and setup of a DICN system 

(See 

Annex I

"Installation examples for a DICN configuration" on

page 9

)

For a system with chillers in a DICN configuration, the chillers have to
be connected as shown in the figure below.

Make the connection as shown on the wiring diagram using an
AWG20/22 shielded cable, made up of a twisted pair plus shield.

Pay attention to the polarity! TX+ on one chiller must be connected to
TX+ on another chiller. The same for TX– and GND.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance with the
wiring diagram supplied with the unit and the instructions
given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.

NOTE

Verify on the wiring diagram all electrical actions
mentioned below, in order to understand the operation
of the unit more deeply.

Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).

A pump interlock contact must be installed in series
with the contact of the flowswitch
  to prevent the
unit from operating without water flow. A terminal is
provided in the switch box for the electrical connection
of the interlock contact.
For units in a DICN configuration, every chiller can
either have an individual circulation pump or 1 pump
can discharge water in a distributor that leads water to
several chillers.
In both cases, all units must be equipped with an
interlock contact!

NOTE

Normally the unit will not operate if there is no flow
thanks to the standard installed flowswitch.
But as to have a double safety, you must  install
the pump interlock contact in series with the
contact of the flowswitch.
Operating the unit without flow will result in very
severe damage to the unit (freezing of the
evaporator).

1

2

3

4

Содержание EWAP400MBYNN

Страница 1: ...INSTALLATION MANUAL EWAP400MBYNN EWAP460MBYNN EWAP540MBYNN Packaged air cooled water chillers...

Страница 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Страница 3: ...nderung 03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med...

Страница 4: ...grills BMS Connection MODBUS J BUS BACNET LON Inverter fans Heat recovery High ESP fans Features Stepless capacity control 15 100 Evaporator heater tape Glycol application for leaving evaporator wate...

Страница 5: ...the unit and the floor is flat to prevent vibration and noise generation 2 The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet refer to the operatio...

Страница 6: ...or I beam frame to support the unit on the roof or it can be installed on a concrete base Ground level mounted The unit must be installed on a solid base It is recommended to fix the unit on a concret...

Страница 7: ...To assure proper operation of the unit the water flow through the evaporator must be within the operation range as specified in the table below and a minimum water volume is required in the system Th...

Страница 8: ...note the following Switch for remote on off Units with status or will be controlled by the remote on off switch connected to the chiller defined as Units with status are controlled by the switch conne...

Страница 9: ...not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for...

Страница 10: ...s to comply Defining of the changeable digital analog inputs and outputs Besides locked inputs and outputs there are a number of changeable inputs and outputs of which the function can be chosen from...

Страница 11: ...from a supervisory system If set to no the supervisory system can only read out values but cannot modify them used to address the PCB indicates the communication protocol If the optional gateway is us...

Страница 12: ...ll units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master u...

Страница 13: ...em configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this buffer One unit s...

Страница 14: ...Installation manual 11 EWAP400 540MBYNN Packaged air cooled water chillers 4PW22678 1B NOTES...

Страница 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergenc...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22678 1B...

Отзывы: