Daikin EWAP400MBYNN Скачать руководство пользователя страница 6

Installation manual

3

EWAP400~540MBYNN

Packaged air-cooled water chillers

4PW22678-1B

U

NPACKING

 

AND

 

PLACING

 

THE

 

UNIT

1

Remove the wooden beams from the unit.

2

Install vibration mountings in case of a roofmounted unit or other
installation where noise and vibration might be an impediment.

3

Set the unit on a solid and level foundation.

Ground level mounting

Fix anchor bolts into the concrete foundation. When finally fixing
the unit by means of these anchor bolts, make sure that the
washers for channel DIN434, and both field supplied rubber
plates and field supplied raw cork or rubber sheets for better
vibration protection, are installed as indicated.

The concrete foundation should approximately be 100 mm
higher than the floor level for ease of plumbing work and better
drain.

Make sure that the foundation surface is even and flat.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R407C

GWP

(1)

 value:

1652.5

(1)

 GWP = global warming potential

The refrigerant quantity is indicated on the unit name plate.

P

REPARING

CHECKING

 

AND

 

CONNECTING

 

THE

 

WATER

 

CIRCUIT

The units are equipped with a water inlet and water outlet for
connection to a chilled water circuit. This circuit must be provided by
a licensed technician and must comply with all relevant European
and national regulations.

1

Preparing the unit for connection to the water circuit

A box containing 

 couplings and a filter is delivered

with the unit.

As a general rule for this and other
units, it is recommended to check the
insertion depth of the water
temperature sensors into the
connection pipes prior to operation
(see figure).

Connecting the filter

Roof mounted:

The unit must be installed on  
steelchannel or I-beam frame to support 
the unit on the roof, or it can be installed 
on a concrete base.

Ground level mounted:

The unit must be installed on a solid 
base. It is recommended to fix the unit on 
a concrete base with anchor bolts.

1

Anchor bolt

2

Washer

3

Rubber plate

4

Raw cork or rubber sheet

5

Ground

6

Concrete floor

7

Ditch

Model

A

B

C

D

E

anchor bolt size

Qty

EWAP400

5906

2210

1700

1989

2125

M16x200

8

EWAP460

5906

2210

1700

1989

2125

M16x200

8

EWAP540

5906

2210

1700

1989

2125

M16x200

8

NOTE

The measurement tabulated is based on the fact
the base is made in the ground or on a concrete
floor. In case the base is made on a rigid floor, it is
possible to include thickness of concrete floor in
that of the base.

In case a base is made on concrete floor, make
sure to provide a ditch as shown. It is important to
extract drainage regardless of whether a base is
made in the ground or on the concrete floor (ditch-
sewerage).

Ingredient ratio of the concrete is: cement 1, sand
2 and gravel 3. Insert iron bars of Ø10 mm at
every interval of 300 

mm. The edge of the

concrete base should be planed.

>200

>350

100

>100

50

X

X

>B

>A

C

>B

E

D

C

1

2
3+4

5

6

7

X-X

If air or dirt gets in the water circuit, problems may occur. 
Therefore, always take into account the following when
connecting the water circuit:

1.

Use clean pipes only.

2.

Hold the pipe end downwards when removing burrs.

3.

Cover the pipe end when inserting it through a wall so that
no dust and dirt enter

1

Water inlet of the evaporator

2

 coupling

3

Counter pipe

4

Field water piping circuit

5

Water inlet temperature sensor

6

Filter

7

Filter end cap

The filter kit supplied with the unit must be
installed in front of the evaporator water inlet by
means of the supplied 

 couplings as

shown in the figure. The filter has holes of
diameter 1.0 mm and secures the evaporator
against clogging.

Improper installation of the supplied filter will
result in severe damage of the equipment
(freezing of the evaporator).

Victaulic

®

2

3

4

6

5

1

7

2

2

Victaulic

®

 50 mm

Victaulic

®

Содержание EWAP400MBYNN

Страница 1: ...INSTALLATION MANUAL EWAP400MBYNN EWAP460MBYNN EWAP540MBYNN Packaged air cooled water chillers...

Страница 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Страница 3: ...nderung 03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med...

Страница 4: ...grills BMS Connection MODBUS J BUS BACNET LON Inverter fans Heat recovery High ESP fans Features Stepless capacity control 15 100 Evaporator heater tape Glycol application for leaving evaporator wate...

Страница 5: ...the unit and the floor is flat to prevent vibration and noise generation 2 The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet refer to the operatio...

Страница 6: ...or I beam frame to support the unit on the roof or it can be installed on a concrete base Ground level mounted The unit must be installed on a solid base It is recommended to fix the unit on a concret...

Страница 7: ...To assure proper operation of the unit the water flow through the evaporator must be within the operation range as specified in the table below and a minimum water volume is required in the system Th...

Страница 8: ...note the following Switch for remote on off Units with status or will be controlled by the remote on off switch connected to the chiller defined as Units with status are controlled by the switch conne...

Страница 9: ...not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for...

Страница 10: ...s to comply Defining of the changeable digital analog inputs and outputs Besides locked inputs and outputs there are a number of changeable inputs and outputs of which the function can be chosen from...

Страница 11: ...from a supervisory system If set to no the supervisory system can only read out values but cannot modify them used to address the PCB indicates the communication protocol If the optional gateway is us...

Страница 12: ...ll units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master u...

Страница 13: ...em configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this buffer One unit s...

Страница 14: ...Installation manual 11 EWAP400 540MBYNN Packaged air cooled water chillers 4PW22678 1B NOTES...

Страница 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergenc...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22678 1B...

Отзывы: