Installation manual

7

EWAP400~540MBYNN

Packaged air-cooled water chillers

4PW22678-1B

C

USTOMIZATION

 

IN

 

THE

 

SERVICE

 

MENU

To change a setting in the service menu:

1

Enter the usersettings menu as indicated in the operation
manual and press the 

h

 key to go to the last screen to enter the

service menu (this is only possible if the unit is off).

2

Enter the correct password using the 

h

  and 

g

  keys. The

password can be found in the service manual.

3

Press 

q

 to confirm the password and enter the service menu.

4

Go to the screen which contains the parameter to be modified by
using the 

h

 and 

g

 keys.

5

Position the cursor behind the parameter to be modified using
the 

q

 key.

6

Select the appropriate setting using the 

h

 and 

g

 keys.

7

Press 

q

 to confirm the modification. When the modification has

been confirmed, the cursor switches to the next parameter
which can now be configured.

8

Place the cursor in the top left corner of the screen when you
are finished changing the parameters on this screen.

9

Repeat from instruction 4 onwards to modify other parameters.

Setting of the minimum outlet water temperature

It is possible to change the minimum outlet water temperature
(

) in the service menu. Before lowering the minimum

outlet water temperature:

Make sure that sufficient glycol is added to the water system
according to the table.

Make sure that the low pressure safety is lowered according to
the table.

Defining a unit in a setup of a DICN system

Change the setting of 

 

 to 

 on each unit.

Setting the password for safety reset

To  avoid resetting of safeties by unqualified persons, the user
password is asked by default when resetting a sefety.

This password however can be changed to 

  

 or to

.

Setting of compressor running hours

When the displayed running hours do not comply with the actual
running hours of the compressor it is possible to change the running
hours to comply.

Defining of the changeable digital/analog inputs and outputs

Besides locked inputs and outputs there are a number of changeable
inputs and outputs of which the function can be chosen from several
possibilities.

Possible functions for changeable digital inputs are:

: no function is appointed to the changeable digital input.

: no function is appointed to the changeable digital input,

but the input status can be read in the "input/output" menu.

 

: to switch between setpoints.

 

: to remotely switch the unit on or off.

 

:  to limit the capacity of the unit to the

entered values.

Possible functions for the changeable digital output are:

 

: no function is appointed to the changeable digital

output.

 

: no function is appointed to the changeable digital

output, but the output is closed.

   

:  can be used to steer a second evaporator

pump.

 

: indicates when the unit is working at 100%.

 

: to control a 3-way water valve when the unit is

working in free cooling state.

Possible configurations for the changeable analog input are:

: no function is appointed to the changeable analog input.

 

:

 

:

:

:

This allows the user to define a setpoint in function of an analog input
as mentioned above. Refer to 

"Defining the setpoint signal setting" on

page 7

.

   

: to control the leaving water temperature of

a DICN system.

Defining the setpoint signal setting

The setpoint signal is used to change the setpoint by an external
analog input signal on a stand alone unit or on Slave 1 in a DICN
system.

Example

All customized settings must be done by a licensed
technician.

minimum outlet water (

)

2°C

0°C

–5°C

–10°C

Weight of ethylene glycol

(%)

10

20

30

40

Weight of propylene glycol (%)

15

25

35

40

Low pressure setting

(bar)

1.3

1.1

0.6

0.2

Improper setting of the minimum outlet water temperature
can result in severe damage of the equipment.

NOTE

Since inadequate resetting of safeties can damage the
machine, it is advised to keep the default setting of

  

.

in setpoints menu

in service menu


Remark

!  

 is only 

available when input 

 (

 or 

) is selected.

Result

Display in readout menu

A

at 0 V 

 12.0°C

 " #

B

at 1 V 

 12.0°C + 5.0°C = 17.0°C

 " $#

%  " #

   " #

  " $#

  " $#

&' (

""

!  " )#

B

1 V

A

0 V

Содержание EWAP400MBYNN

Страница 1: ...INSTALLATION MANUAL EWAP400MBYNN EWAP460MBYNN EWAP540MBYNN Packaged air cooled water chillers...

Страница 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Страница 3: ...nderung 03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med...

Страница 4: ...grills BMS Connection MODBUS J BUS BACNET LON Inverter fans Heat recovery High ESP fans Features Stepless capacity control 15 100 Evaporator heater tape Glycol application for leaving evaporator wate...

Страница 5: ...the unit and the floor is flat to prevent vibration and noise generation 2 The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet refer to the operatio...

Страница 6: ...or I beam frame to support the unit on the roof or it can be installed on a concrete base Ground level mounted The unit must be installed on a solid base It is recommended to fix the unit on a concret...

Страница 7: ...To assure proper operation of the unit the water flow through the evaporator must be within the operation range as specified in the table below and a minimum water volume is required in the system Th...

Страница 8: ...note the following Switch for remote on off Units with status or will be controlled by the remote on off switch connected to the chiller defined as Units with status are controlled by the switch conne...

Страница 9: ...not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for...

Страница 10: ...s to comply Defining of the changeable digital analog inputs and outputs Besides locked inputs and outputs there are a number of changeable inputs and outputs of which the function can be chosen from...

Страница 11: ...from a supervisory system If set to no the supervisory system can only read out values but cannot modify them used to address the PCB indicates the communication protocol If the optional gateway is us...

Страница 12: ...ll units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master u...

Страница 13: ...em configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this buffer One unit s...

Страница 14: ...Installation manual 11 EWAP400 540MBYNN Packaged air cooled water chillers 4PW22678 1B NOTES...

Страница 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergenc...

Страница 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22678 1B...

Отзывы: