8 Troubleshooting

Operation manual

16

EWAA011~016DA + EWYA009~016DA

Packaged air-cooled water chillers

and packaged air to water heat pumps

4P620244-1B – 2021.02

: Error

: Malfunction

You  can  get  a  short  and  a  long  description  of  the  malfunction  as
follows:

1

Press the left dial to open the main menu and go to

Malfunctioning

.

Result: 

A short description of the error and the error

code is displayed on the screen.

2

Press   in the error screen.

Result: 

A long description of the error is displayed

on the screen.

8.2

To check the malfunction history

Conditions: 

The user permission level is set to advanced end user.

1

Go to [8.2]: 

Information

 > 

Malfunction history

.

You see a list of the most recent malfunctions.

8.3

Symptom: You are feeling too cold
(hot) in your living room

Possible cause

Corrective action

The desired room temperature is
too low (high).

Increase (decrease) the desired
room temperature. See 

"5.6.2 To

change the desired room
temperature"

 [

4

 10].

If the problem recurs daily, do
one of the following:

▪ Increase  (decrease)  the  room

temperature  preset  value.  See
the user reference guide.

▪ Adjust  the  room  temperature

schedule.  See 

"5.7  Schedule

screen: Example"

 [

4

 11].

The desired room temperature
cannot be reached.

Increase the desired leaving
water temperature in accordance
with the heat emitter type. See

"5.6.3 To change the desired
leaving water temperature"

 [

4

 11].

The weather-dependent curve is
set incorrectly.

Adjust the weather-dependent
curve. See 

"5.8 Weather-

dependent curve"

 [

4

 13].

8.4

Symptom: Unit failure

When  the  heat  pump  fails  to  operate,  the  optional  external  backup
heater kit can serve as an emergency heater. It then takes over the
heat load either automatically or by manual interaction.

▪ When 

Emergency

 is set to 

Automatic

 (or 

auto  SH  normal/DHW

off

)

(1)

  and  a  heat  pump  failure  occurs,  the  backup  heater

automatically takes over the heat load.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater can take over the heat load or not.

▪ When 

Emergency

 is set to 

auto  SH  reduced/DHW  off

 (or 

auto

SH  reduced/DHW  on

)

(2)

  and  a  heat  pump  failure  occurs,  space

heating is reduced.

Similarly  as  in 

Manual

  mode,  the  unit  can  take  the  full  load  with

the  backup  heater  if  the  user  activates  this  via  the

Malfunctioning

 main menu screen.

When the unit fails, 

 or 

 will appear on the user interface.

Possible cause

Corrective action

Unit is damaged.

See 

"8.1 To display the help text

in case of a malfunction"

 [

4

 15].

INFORMATION

When  the  backup  heater  takes  over  the  heat  load,
electricity consumption will be considerably higher.

8.5

Symptom: The system is making
gurgling noises after
commissioning

Possible cause

Corrective action

There is air in the system.

Purge air from the system.

(a)

Incorrect hydraulic balance.

To be performed by the installer:

1

Perform  hydraulic  balancing
to  assure  that  the  flow  is
correctly 

distributed

between the emitters.

2

If  hydraulic  balancing  is  not
sufficient,  change  the  pump
limitation  settings  ([9-0D]
and [9-0E] if applicable).

Various malfunctions.

Check if 

 or 

 is displayed

on the home screen of the user
interface. See 

"8.1 To display the

help text in case of a
malfunction"

 [

4

 15] for more

information about the
malfunction.

(a)

We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:

WARNING

Air  purging  heat  emitters  or  collectors.

  Before  you

purge  air  from  heat  emitters  or  collectors,  check  if 

  or

 is displayed on the home screen of the user interface.

▪ If not, you can purge air immediately.

▪ If  yes,  make  sure  that  the  room  where  you  want  to

purge air is sufficiently ventilated. 

Reason:

 Refrigerant

might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.

(1)

auto SH normal/DHW off

 has the same effect as 

Automatic

, but should NOT be used because there is no domestic hot water.

(2)

auto SH reduced/DHW on

 has the same effect as 

auto SH reduced/DHW off

, but should NOT be used because there is no domestic hot

water.

Содержание EWAA011-016DAV3P

Страница 1: ...air to water heat pumps English Operation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA011 016DAV3P EWAA011 016DAW1P EWAA011 016DAV3P H EWAA011 016DAW1P H EWYA009...

Страница 2: ...settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future reference Target audience End users...

Страница 3: ...ans that electrical and electronic products may NOT be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil...

Страница 4: ...and subsequently into the room when you purge air from the heat emitters or collectors 3 About the system Depending on the system layout the system can Heat up a space Cool down a space INFORMATION H...

Страница 5: ...ature b Desired room temperature To change the desired leaving water temperature You can use the leaving water temperature setpoint screen to read out and adjust the desired leaving water temperature...

Страница 6: ...used for SD cards USB connector With a USB memory stick the installer can Update the software This requires a correct config file on the USB memory stick Import the settings generated by E Configurato...

Страница 7: ...Schedule Level 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 4 Space heating cooling Operation mode Operation mode schedule 1 9 Room comfort setpoint Heating comf...

Страница 8: ...r unit f Main zone f1 Installed room thermostat type Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Unit operation...

Страница 9: ...ormation about the outdoor unit 9 Installer settings Restriction Only for the installer Gives access to advanced settings A Commissioning Restriction Only for the installer Perform tests and maintenan...

Страница 10: ...le Unit pump ON OFF In menu You can read out 8 6 Operation modes Current operation mode Example Defrost oil return mode 8 7 About Version information about the system 8 8 Connection status Information...

Страница 11: ...g water temperature 1 Go to 2 Main zone or 3 Additional zone Main zone 2 Additional zone 3 2 Adjust the desired leaving water temperature 20 C 2 a b Main zone 12 C 3 a b Additional zone a Actual leavi...

Страница 12: ...lear an action set its time as the time of the previous action 4 Confirm the changes Result The schedule for Monday is defined The value of the last action is valid until the next programmed action In...

Страница 13: ...mperature the unit relies on its weather dependent curve This curve defines how much the leaving water temperature must be at different outdoor temperatures Because the slope of the curve depends on l...

Страница 14: ...ope offset When slope is selected set slope and go to offset When offset is selected set offset Confirm changes and return to the submenu 5 8 4 Using weather dependent curves Configure weather depende...

Страница 15: ...have to Keep the area around the unit clean Keep the user interface clean with a soft damp cloth Do NOT use any detergents Regularly check if the water pressure is above 1 bar Refrigerant This produc...

Страница 16: ...to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not When Emergency is set to auto SH reduced DHW off or auto SH reduced DHW on 2 and a heat...

Страница 17: ...by installer 10 1 Configuration wizard Setting Fill in System Backup heater type 9 3 1 Emergency 9 5 Number of zones 4 4 Glycol Filled system overview field setting E 0D Backup heater Voltage 9 3 2 C...

Страница 18: ......

Страница 19: ......

Страница 20: ...4P620244 1B 2021 02 Copyright 2020 Daikin 4P620244 1 B 0000000W Verantwortung f r Energie und Umwelt...

Отзывы: