8 Configuration
Installation manual
28
EWAA004~008D2 + EWYA004~008D2
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688014-1A – 2022.05
5678
Installer
Advanced user pin code
The
Advanced user
pin code is
1234
. Additional menu items for the
user are now visible.
1234
Advanced user
User pin code
The
User
pin code is
0000
.
0000
User
To access the installer settings
1
Set the user permission level to
Installer
.
2
Go to [9]:
Installer settings
.
To modify an overview setting
Example:
Modify [1‑01] from 15 to 20.
Most settings can be configured via the menu structure. If for any
reason it is required to change a setting using the overview settings,
then the overview settings can be accessed as follows:
1
Set the user permission level to
Installer
. See
change the user permission level"
27].
—
2
Go to [9.I]:
Installer settings
>
Overview
field settings
.
3
Turn the left dial to select the first part of the setting
and confirm by pressing the dial.
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0
1
2
3
4
Turn the left dial to select the second part of the
setting
00
01
15
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
1
5
Turn the right dial to modify the value from 15 to 20.
00
01
20
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
1
6
Press the left dial to confirm the new setting.
7
Press the center button to go back to the home
screen.
INFORMATION
When you change the overview settings and you go back
to the home screen, the user interface will show a popup
screen and request to restart the system.
When confirmed, the system will restart and recent
changes will be applied.
8.2
Configuration wizard
After first power ON of the system, the user interface starts a
configuration wizard. Use this wizard to set the most important initial
settings for the unit to run properly. If required, you can afterwards
configure more settings. You can change all these settings via the
menu structure.
8.2.1
Configuration wizard: Language
#
Code
Description
[7.1]
N/A
Language
8.2.2
Configuration wizard: Time and date
#
Code
Description
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. These settings can be changed
during initial configuration or via the menu structure [7.2]:
User settings
>
Time/date
.
8.2.3
Configuration wizard: System
Backup heater type
#
Code
Description
[9.3.1]
[E‑03]
▪ 0:
No heater
▪ 1:
External heater
Emergency
When the heat pump fails to operate, the optional external backup
heater kit can serve as an emergency heater. It then takes over the
heat load either automatically or by manual interaction.
▪ When
Emergency
is set to
Automatic
(or
auto SH normal/DHW
off
)
(1)
and a heat pump failure occurs, the backup heater
automatically takes over the heat load.
▪ When
Emergency
is set to
Manual
and a heat pump failure
occurs, the space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main menu screen and confirm whether the
backup heater can take over the heat load or not.
(1)
auto SH normal/DHW off
has the same effect as
Automatic
, but should NOT be used because there is no domestic hot water.