5 Operation

Operation manual

14

EWAA004~008D + EWYA004~008D

Packaged air-cooled water chillers

and packaged air to water heat pumps

4P688015-1C – 2022.09

4

Select 

Paste

.

Delete

Edit

Copy

Paste

Result:

Mon

Sat

Wed

Fri

Thu

Tue

Sun

User defined 1

C

5

Repeat this action for all other weekdays.

Mon

Sat

Wed

Fri

Thu

Tue

Sun

User defined 1

C

To program the schedule for Saturday and copy it to Sunday

1

Select 

Saturday

.

2

Select 

Edit

.

3

Use the left dial to select an entry and edit the entry
with the right dial.

0

8:00

23:00

--:--

22°C
20°C

--

12

24

Sat

4

Confirm the changes.

5

Select 

Saturday

.

6

Select 

Copy

.

7

Select 

Sunday

.

8

Select 

Paste

.

Result:

Mon

Sat

Wed

Fri

Thu

Tue

Sun

User defined 1

C

To rename the schedule

1

Select the name of the current schedule.

Mon

Sat

Wed

Fri

Thu

Tue

Sun

User defined 1

2

Select 

Rename

.

Delete

Rename

Select

3

(optional) To delete the current schedule name,
browse through the character list until 

 is

displayed, then press to remove the previous
character. Repeat for each character of the schedule
name.

4

To name the current schedule, browse through the
character list and confirm the selected character.
The schedule name can contain up to 15 characters.

5

Confirm the new name.

INFORMATION

Not all schedules can be renamed.

5.8

Weather-dependent curve

5.8.1

What is a weather-dependent curve?

Weather-dependent operation

The  unit  operates  'weather-dependent'  if  the  desired  leaving  water
temperature is determined automatically by the outdoor temperature.
It  therefore  is  connected  to  a  temperature  sensor  on  the  North  wall
of  the  building.  If  the  outdoor  temperature  drops  or  rises,  the  unit
compensates  instantly.  Thus,  the  unit  does  not  have  to  wait  for
feedback  by  the  thermostat  to  increase  or  decrease  the  leaving
water  temperature.  Because  it  reacts  more  quickly,  it  prevents  high
rises and drops of the indoor temperature.

Advantage

Weather-dependent operation reduces energy consumption.

Weather-dependent curve

To  be  able  to  compensate  for  differences  in  temperature,  the  unit
relies on its weather-dependent curve. This curve defines how much
the  leaving  water  temperature  must  be  at  different  outdoor
temperatures.  Because  the  slope  of  the  curve  depends  on  local
circumstances  such  as  climate  and  the  insulation  of  the  house,  the
curve can be adjusted by an installer or user.

Types of weather-dependent curve

There are 2 types of weather-dependent curves:

▪ 2-points curve

▪ Slope-offset curve

Which type of curve you use to make adjustments, depends on your
personal  preference.  See 

"5.8.4  Using  weather-dependent

curves"

 [

4

 15].

Availability

The weather-dependent curve is available for:

▪ Main zone - Heating

▪ Main zone - Cooling

▪ Additional zone - Heating

▪ Additional zone - Cooling

INFORMATION

To  operate  weather-dependent,  correctly  configure  the
setpoint  of  the  main  zone  and  additional  zone.  See

"5.8.4 Using weather-dependent curves"

 [

4

 15].

Содержание EWAA004D2V3P-H

Страница 1: ...heat pumps English Operation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA004D2V3P EWAA006D2V3P EWAA008D2V3P EWAA004D2V3P H EWAA006D2V3P H EWAA008D2V3P H EWYA004...

Страница 2: ...ler to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If NOT request him to do so Keep the documentation for future referen...

Страница 3: ...means that electrical and electronic products may NOT be mixed with unsorted household waste Do NOT try to dismantle the system yourself dismantling the system treatment of the refrigerant of oil and...

Страница 4: ...uit and subsequently into the room when you purge air from the heat emitters or collectors 3 About the system Depending on the system layout the system can Heat up a space Cool down a space INFORMATIO...

Страница 5: ...eating cooling On On Room C 2 2 Set operation to On or Off To change the desired room temperature During room temperature control you can use the room temperature setpoint screen to read out and adjus...

Страница 6: ...User reference guide 5 Operation INFORMATION Heating is only applicable in case of reversible models 5 1 User interface Overview The user interface has the following components a b c d a Slot for WLA...

Страница 7: ...how a help text related to the current page if available e Right dial The LCD shows an arc on the right side of the display when you can use the right dial Turn then press the right dial Change a valu...

Страница 8: ...Restrictions 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 4 Space heating cooling Operation mode Operation mode schedule 1 9 Room comfort setpoint Heating comfort...

Страница 9: ...unit f Main zone f1 Installed room thermostat type Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Unit operation...

Страница 10: ...ata and information about the outdoor unit 9 Installer settings Restriction Only for the installer Gives access to advanced settings A Commissioning Restriction Only for the installer Perform tests an...

Страница 11: ...On or Off 5 5 Reading out information To read out information 1 Go to 8 Information Possible read out information In menu You can read out 8 1 Energy data Produced energy consumed electricity and con...

Страница 12: ...Go to 1 Room Room 1 2 Adjust the desired room temperature 21 C 1 a b Room a Actual room temperature b Desired room temperature If scheduling is on after changing the desired room temperature The tempe...

Страница 13: ...lear the content of a day schedule 1 Select the day of which you want to clear the content For example Friday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 2 Select Delete Delete Edit Copy 3 Select OK...

Страница 14: ...nt operation The unit operates weather dependent if the desired leaving water temperature is determined automatically by the outdoor temperature It therefore is connected to a temperature sensor on th...

Страница 15: ...ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature for all...

Страница 16: ...es At cold outdoor temperatures Y2 a Y1 a X1 a X2 a OK Cold OK Hot You feel Fine tune with setpoints At regular outdoor temperatures At cold outdoor temperatures Y2 a Y1 a X1 a X2 a Cold OK Cold Cold...

Страница 17: ...he error and the error code is displayed on the screen 2 Press in the error screen Result A long description of the error is displayed on the screen 8 2 To check the malfunction history Conditions The...

Страница 18: ...mitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that...

Страница 19: ......

Страница 20: ...4P688015 1C 2022 09 Copyright 2022 Daikin 4P688015 1 C 00000000 Verantwortung f r Energie und Umwelt...

Отзывы: