Checking the Inputs and Outputs
ESIE11-02
3–18
3
1
3
4
5
3.6
Checking the Power Supply and Fuses: EUWA*5-24KBZW1 and
EUWY*5-24KBZW1
Overview
The table below contains an overview of the circuits, the voltage and their fuse codes.
Circuit
Wiring code
Type / voltage
Fuse code
Main supply
L1 + L2 + L3 + N
3 phases / 400 V AC
F1+F2+F3
Control circuit I/O PCB
L1 + N
L3 + N
1 phase / 230 V AC
1 phase / 230 V AC
F4
F1U
Control circuit controller
TR1-sec.
24 V AC
F3U, F5U
Control circuit (pump) for
EUWAN5-24KBZW1
X1M 8-7
24 V AC
F6
Fan circuit for
EUWA*5-12KBZW1
L1 + N
1 phase / 230 V AC
F7
Fan circuit for
EUWA*18-24KBZW1
L1 + N
1 phase / 230 V AC
F8