ESIE11-02
Functional Description
Part 2 – Functional Description
2–17
3
2
4
5
1
1.13
Freeze-up Control: EUWA*5-24KBZW1 and EUWY*5-24KBZW1
Functional
description
The freeze-up control is a protection against ice formation in the water circuit at the evaporator outlet.
Characteristics
The table below contains the characteristics of the freeze-up protection.
Characteristics for
glycol option
The table below contains the characteristics of the freeze-up protection for the glycol option.
Characteristics
Freeze-up protection
Control device
Sensor
Diagram name
R4T
Activation
Outlet water temperature < 4°C
Result: The unit is disabled.
Reset
Manually on controller if temperature > 7.5°C
(4°C + anti-freeze hysteresis).
Result: The circuit restarts.
ZL
Activation
Outlet water temperature < -11.5°C
Reset
Manually on controller if temperature > -8°C
(-11.5°C + anti-freeze hysteresis).
ZH
Activation
Outlet water temperature < -6.5°C
Reset
Manually on controller if temperature > -3°C
(-6.5°C + anti-freeze hysteresis).
Содержание EUWY 24KBZW1 Series
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...