EUWAC5~10FZ

Packaged air-cooled water chillers

4PW14037-1D

Installation and operation manual

2

Options and features 

(1)

Options

Glycol application for chilled water temperature down to –10 
or –5°C. (**)
(**) Do not use internally Zinc-coated or galvanized steel pipes
for the additional waterpiping.

BMS-connection (MODBUS/J-BUS, BACNET)

Remote user controlller (optional kit EKRUMC)

Features

Lower ambient temperature operation (–10°C 

DB) due to

integrated head pressure control.

Standard operation range

M

AIN

 

COMPONENTS

 

(See figure 1)

S

ELECTION

 

OF

 

LOCATION

The EUWAC unit should be installed in a location that meets the
following requirements:

1

The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.

2

The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (See
figure 2 and figure 3.)

If several units are being installed side by side in parallel, the
minimum service space between them must be taken into
account.

3

There is no danger of fire due to leakage of inflammable gas.

4

Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.

5

Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.

6

Ensure that water cannot cause any damage to the location in
case it drips out of the unit (e.g. in case of a blocked drain pipe).

7

A drain is provided and there is
enough space to install a trap
with a minimum fall of 75 mm
between the drain outlets of the
unit and the drain.

The equipment is not intended for use in a potentially explosive
atmosphere.

I

NSPECTING

 

AND

 

HANDLING

 

THE

 

UNIT

The EUWAC units are packed in a cardboard box and attached on a
wooden pallet.

At delivery, the package should be checked and any damage should
be reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1.

Follow the instructions marked by the symbols on the package:

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

Do not use straps to move the unit.

2.

Lift the unit preferably with a fork-lift, a manual pallet mover or a
crane and belts.

3.

When lifting the unit with a crane, always use protectors to prevent
belt damage and pay attention to the position of the unit’s centre of
gravity. 

4.

Bring the unit as close to its final installation position in its original
package to prevent damage during transport. 

U

NPACKING

 

AND

 

PLACING

 

THE

 

UNIT

1

Cut the straps and remove the cardboard box from the unit. 

2

Remove the four screws fixing the unit to the pallet.

3

Lift the unit from the pallet and place it on its installation position.

4

Connect the air inlet (lower part of the unit) to the air inlet
ducting and the air outlet (upper part of the unit) to the air outlet
ducting. Always provide a flexible connection between the
ducting flanges of the unit and the ducts to prevent vibrations
and noise generation.

(1) Refer to the chapter “

Operating the unit

” or engineering data book for the 

complete list of specifications and options.

Standard operation range

Protect the water piping against water freezing during winter 
period

A

Outdoor ambient temperature (°C DB)

B

Leaving water temperature evaporator (°C)

C

Glycol

D

Water

E

For nominal E.S.P. of 60 Pa (8 Hp) and of 72 Pa (10 Hp)

F

For E.S.P. of 150 Pa (8+10 Hp only)

1

Upper service plate

2

Lower service plate

3

Water inlet connection

4

Water outlet connection

5

Power supply intake

6

Digital controller

7

Drain outlet

8

Low pressure gauge (suction pressure)

9

High pressure gauge (discharge pressure)

10

Air inlet ducting flanges

11

Air outlet ducting flanges

12

Identification plate

B

A

36

43
40

4

21 25

0

0

–5

–10

–15

–20

11 15

40

–10

–20

50

ZL

ZH

C

D

E

E
F

E
F

75 mm

Содержание EUWAC10FZW1

Страница 1: ...INSTALLATION AND OPERATION MANUAL EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1 Packaged air cooled water chillers...

Страница 2: ...D E F G H I J K L M N O P Q R EUWAC5FZ mm 243 311 243 1345 343 125 765 71 58 629 108 25 796 605 735 578 600 795 EUWAC8FZ mm 163 800 162 1290 267 98 815 71 60 951 111 25 1125 605 288 975 600 1122 EUWAC...

Страница 3: ...en i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob u...

Страница 4: ...and used for cooling applications only The units are available in 3 standard sizes with nominal cooling capacities ranging from 11 2 to 22 6 kW The EUWAC packaged air cooled water chillers can be comb...

Страница 5: ...dboard box and attached on a wooden pallet At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account...

Страница 6: ...the water circuit 1 Use clean pipes only 2 Hold the pipe end downwards when removing burrs 3 Cover the pipe end when inserting it through a wall so that no dust and dirt enter WATER CHARGE FLOW AND Q...

Страница 7: ...d that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public sys tem It is the responsibility of the installer or user of the equip me...

Страница 8: ...lter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the expansion valve and tubes Thermostatic expansion valve The liquid refrigerant coming from th...

Страница 9: ...ter becomes too low in order to prevent freezing of the water during operation When the outlet water temperature returns to normal the protector resets automatically but the controller needs to be res...

Страница 10: ...er operation of the drain Pour some water into the drain pan and check whether the water evacuates freely through the drain Water supply Fill the water piping taking into account the minimum water vol...

Страница 11: ...9 Consulting actual operational information on page 9 Resetting alarms on page 9 Resetting warnings on page 10 Switching the EUWAC unit on To switch the EUWAC unit on proceed as follows 1 When the on...

Страница 12: ...er temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of direct parameters without saving the modified parameter The inlet water t...

Страница 13: ...t of direct parameters is accessible by pressing the R key for approximately 5 seconds When scrolling through the list of direct parameters using the A and or Z key the parameters appear in the follow...

Страница 14: ...aying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifications The i...

Страница 15: ...t other user parameters before saving the modifications select another user parameter using the A and or Z key and then repeat from instruction 3 onwards 7 To save the modifications press the E key To...

Страница 16: ...without saving the modifications The inlet water temperature reappears on the display TROUBLESHOOTING This section provides useful information for diagnosing and correct ing certain troubles which may...

Страница 17: ...freely Air flow in the unit too low or outdoor temperature too high Clean the air heat exchanger properly RESET After temperature decrease the thermal protector is reset automatically If the protecto...

Страница 18: ...leak is detected call your local Daikin dealer Check the working pressure of the unit Refer to paragraph Working pressure on page 8 in the chapter Switching the EUWAC unit on 6 Compressor Check on oi...

Страница 19: ...5 10 5 15 20 15 30 25 40 35 50 C 45 5 Hp 8 Hp 10 Hp General specifications IN OUT IN OUT IN OUT Nominal air flow m3 min 70 70 100 100 125 125 long side W mm 763 341 952 802 1102 938 short side P mm 6...

Страница 20: ...ESP External static pressure AF Air flow 1 ESP with pulley closed factory setting 2 ESP with pulley 1 turn open 3 ESP with pulley 2 turns open 4 ESP with pulley 3 turns open 5 ESP with pulley 4 turns...

Страница 21: ...4 4 6 7 16 11 10 12 13 6 7 16 11 10 12 13 2 15 4 5 2 15 3 9 8 1 14 9 8 1 14 5 5 M1C P S4LP 6 P S1HP 7 1 3 9 8 5 4 2 10 10 R3T R4T M11F M11F EUWAC5 EUWAC8 10...

Страница 22: ...4PW14037 1D Copyright Daikin...

Отзывы: