ESIE09-05
Protection Control
Function
35
4.3 Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
[INV compressor]
In discharge pipe temp.
protection control
HTdi>115˚C
Tp>135˚C
HTdi :Value of INV compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Tp :
Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.
or
Discharge pipe protection
control not limited
INV upper limit frequency:
1-step down from current
compressor frequency
INV upper limit frequency: 1-step up
from current compressor frequency
36 Hz Unload
HTdi>115˚C
Tp>135˚C
or
HTdi>135˚C
HTdi>120˚C for 10 min. or more.
or
HTdi<110˚C
Tp<125˚C
&
After 30 sec.
After 20 sec.
HTdi>130˚C
HTdi>120˚C
for 90 sec.
or more.
or
HTdi<100˚C
Tp<110˚C
&
When occurring 3 times within 100 minutes,
the malfunction code “F3” is output.
Discharge pipe
temperature standby
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...