ESIE09-05
Basic Control
Function
25
2.3 Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
Furthermore, when outdoor temperature
≥
20°C, the compressor will run in Step 7 or higher.
When outdoor temperature
≥
18°C, it will run in Step 5 or higher.
When outdoor temperature
≥
12°C, it will run in Step 1 or higher.
850 rpm
715 rpm
580 rpm
445 rpm
360 rpm
285 rpm
400 rpm
250 rpm
0 rpm
M1F
815 rpm
680 rpm
545 rpm
410 rpm
325 rpm
250 rpm
0 rpm
0 rpm
0 rpm
M2F
STEP3
STEP4
STEP5
STEP6
STEP7
STEP8
STEP2
STEP1
STEP0
Cooling
Fan Steps
Upper limit of fan
revolutions: Step 8
Upper limit of outdoor unit
fan revolutions
Step 7
-1 step on
outdoor unit fan
+1 step on
outdoor unit fan
Pc
<2.75MPa
PI control
Pc
>3.24MPa
Lapse of 20 sec.
PI control
PI control
Lapse of 20 sec.
Hold the
current step on
outdoor unit fan
Pc: HP pressure sensor detection value
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...