Operation Mode
ESIE09-05
22
Function
1. Operation Mode
Operation in
stop mode
Pressure
equalization
prior to startup
Startup control
• Cooling startup
control
• Heating startup
control
Oil return IN
conditions are met.
Operation
mode change
Oil return operation
Pump-down
residual
operation
Restart standby
(Compressor stop)
Yes
Yes
No
No
Malfunction/Standby
AHU stop or
thermostat OFF
Normal operation
• Compressor PI control
• Electronic expansion
valve PI control
• Protection control
AHU thermostat ON
Defrost IN
conditions are met.
No
Yes
Defrosting operation
Cooling or heating
operation
AHU thermostat ON
AHU stop or
thermostat OFF
AHU stop or
thermostat OFF
Malfunction/
Standby
Malfunction/
Standby
Note:
In the AHU stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
Malfunction/Standby
(V3152)
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...