ESIE09-05
Troubleshooting by Remote Controller
Troubleshooting
157
Mode
No
Function
Contents and operation method
Remote controller display example
40
Malfunction history
display
Display malfunction history.
The history No. can be changed with the
button.
41
Display of sensor
and address data
Display various types of data.
Select the data to be displayed with the
button. Sensor data
0: Thermostat sensor in remote controller.
1: Suction (or level if DDC-controller connected.
00 = level 1 etc.)
2: Liquid pipe
3: Gas pipe
Address data
8: Cool/heat group address
9: Demand / low noise address
43
Forced fan ON
Manually turn the fan ON by each unit. (When
you want to search for the unit No.)
By selecting the unit No. with the
button,
you can turn the fan of each AHU on (forced ON)
individually.
Hystory No: 1 - 9
1: Latest
Unit 1
Malfunction code
2-U4
Malfunction code
40
(VE007)
Temperature ºC
"
Sensor data display
Unit No.
Sensor type
1 1
2 7
Address
"
Address display
Unit No.
Address type
1 8
1
(VE008)
Unit 1
"!
(VE009)
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...