Model Names of Outdoor Units, Control Box and Expansion Valve Kit
ESIE09-05
4
General Information
1.3 Expansion Valve Kit
Outlook
Expansion valve kit installation drawing:
Model name
Limits for outdoor unit (expansion valve kit).
Depending on the heat exchanger, a connectable EKEXV (expansion valve kit) must be
selected to these limitations.
Saturated suction temperature (SST) = 6°C, SH (superheat) = 5 K, air temperature = 27°C DB /
19°C WB.
Outdoor unit (class)
EKEXV kit
100
EKEXV63~125
125
EKEXV63~140
140
EKEXV80~140
Allowed heat exchanger volume (dm
3
) Allowed heat exchanger capacity (kW)
EKEXV class
Minimum
Maximum
Minimum
Maximum
63
1.66
2.08
6.3
7.8
80
2.09
2.64
7.9
9.9
100
2.65
3.30
10.0
12.3
125
3.31
4.12
12.4
15.4
140
4.13
4.62
15.5
17.6
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание ERQ
Страница 2: ...http splitoff ru tehn doc html...
Страница 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Страница 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Страница 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Страница 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...
Страница 63: ...ESIE09 05 Wiring Diagram of Control Box Control Box 53 3 2 F box http splitoff ru tehn doc html...
Страница 127: ...ESIE09 05 Installation and Operation Manual 117 Part 8 Installation and Operation Manual http splitoff ru tehn doc html...
Страница 240: ...Wiring Diagrams ESIE09 05 230 Appendix 2 2 Field Wiring ERQ 100 125 140 A7V1B http splitoff ru tehn doc html...